DOTECH DPX300-HIAIR Manual del usuario - Página 3
Navegue en línea o descargue pdf Manual del usuario para Interruptor DOTECH DPX300-HIAIR. DOTECH DPX300-HIAIR 3 páginas. Digital pressure switch
PARAMETER
Press PRG button for 3 seconds to change parameters
●
Movement to next menu and storage of set value during parameter setup are performed by SEL button.
●
Set value will be flickering in every 0.5 seconds and change set value using ▲ or ▼ button
●
If there was no input for 3 minutes during setup, it will be returned to operation mode.
●
Setup values will be initialized if pushing PRG button and ▼ button for 10 seconds.
●
OPERATION
MODE
COMPLETE SET
■ PARAMETER TABLE
(PRG Button Push for 3 Sec.)
No
Menu
1
High Pressure Switch Set Value
High Pressure Switch Reset Mode (※1)
2
(Manual / Automatic Reset)
3
High Pressure Switch Releasing Value
4
High Pressure Switch sense delay
5
Low Pressure Switch Set Value
Low Pressure Switch Reset Mode (※1)
6
(Manual / Automatic Reset)
7
Low Pressure Switch Releasing Value
8
Low Pressure Switch Delay Time (※2)
9
Oil Pressure Switch Set Value (※3)
Oil Pressure Switch Reset Mode (※1)
10
(Manual / Automatic Reset)
11
Oil Pressure Switch Releasing Value (※3)
12
Oil Pressure Switch Delay Time (※4)
13
Oil Pressure Switch Control Mode
14
Refrigerant Selection (※5)
15
Low Pressure Offset (※6)
16
High Pressure Offset (※6)
17
Oil Pressure Offset (※6)
(※1) Reset mode : Automatic Reset ( A ): It will be reset automatically when reaching releasing pressure value.Manual reset
(※2) Low pressure switch delay time : If output is activated, it maintenances ON status during minimum ON time even under the OFF condition.
(※3) Oil Pressure Switch Set Value : Differential pressure( ODP ) = Oil pressure – Low pressure
(※4) Oil Pressure Switch Delay Time : Output will be activated after maintaining delay time which is set even though it is
(※5) Refrigerant selection : Display saturation temperature in accordance with selected refrigerant.
(※6) Offset : Offset the differential for pressure sensor. e.g)
If displayed pressure value: 2.0bar and actual pressure value: 2.2bar It is offset by inputting +0.2bar.
PARAMETER
PARAMETER
Press for 3 seconds
MOVEMENT TO
NEXT MENU
Button
MENU
Press for 3 seconds
Code
HPS
HPH
HPF
HPD
LPS
LPH
LPF
LPD
0PS
0PH
0PF
0PD
0DP
R22 (0)= R22
RFY
R23 (1)= R23
LOF
HOF
0OF
( H ): It will not be reset when reaching release pressure value unless users press RST button twice consecutively.
When input switch for compressor operation status (S1) is closed (Normally closed contact (N.C)),
it becomes an ON condition for OPS (Oil Pressure Switch Set Value) output if ODP (Differential pressure valve)is
less than OPS (Oil Pressure Switch Set Value). Output is de-activated if ODP (Differential pressure valve) is
higher than OPF (Oil Pressure Switch Releasing Value) after output is activated.
under the ON condition.
LED lamp will be turned on a light simultaneously with output after flickering during delay time.
SET VALUE
CHANGE
SET VALUE
Button
Unit
Step
bar
0.1
A = Automatic Reset
bar
0.1
sec
1
bar
0.1
A = Automatic Reset
bar
0.1
LPS + 0.1
sec
1
bar
0.1
A = Automatic Reset
bar
0.1
0PS + 0.1
sec
1
0 - L = OP - LP
1 24 (3)= R-124
1 34 (4)= R-134a
1 23 (2)= R-123
404 (5)= R-404a
bar
0.1
bar
0.1
bar
0.1
- 3 -
SET VALUE
SAVE
COMPLETE
Button
Min
Max
Default
0.0
30.0
1 8.5
H = Manual Reset
0.0
HPS - 0.1
1 4.5
0
999
-1.0
15.0
0.3
H = Manual Reset
15.0
1 .3
0
999
0.0
16.0
0.7
H = Manual Reset
16.0
0.9
0
999
60
H - 0 = HP - OP
0-L
407 (6)= R-407c
4 1 0 (7)= R-410a
407
507 (8)= R-507
-1.9
1.9
0.0
-1.9
1.9
0.0
-1.9
1.9
0.0
Custom
Setup
H
0
A
0
H
R20220929