Advanced Mxp-536 Manual - Página 5
Navegue en línea o descargue pdf Manual para Sistemas de E/S Advanced Mxp-536. Advanced Mxp-536 16 páginas. Peripheral zone card
2.2 Basic Configuration
switches (as depicted above).
In Stand Alone mode the address switches are used to configure the EOL setting:
Bit 0
Bit 1
EOL Setting
Off
Off
Default EOL (6K8)
On
Off
4K7
Off
On
3K9
On
On
Not Used (defaults to 6K8)
Note: Bits 2 and 3 current have no function when operating in stand alone mode.
www.advancedco.com
Each card connected to the 485 Communication Line must have its
own address. This address should be set so that it matches the
corresponding card within the Advanced PC Config Tool design.
Configuration Defaults:
-
Earth Monitor Disabled: This is the required condition if the
card is expected to share a ground plane with the parent fire Panel,
or any other card which also provides earth monitoring capabilities.
For example, if multiple Zone cards are located in a remote
enclosure, that requires earth monitoring; only 1 of the cards should
be set to monitoring mode. Slide switch to the ON position to enable
the earth monitor circuit.
-
Radial (Class B) operation. Slide switch to the ON position to
put card into Loop (Class A) mode.
-
Stand Alone Mode. Slide PBUS switch to the ON position to
enable Peripheral Bus Mode.
In Peripheral Bus mode the card address is set using the Address
5