Operation / Task
Damper reference
Date of inspection
Check actuator wiring for damage (where applicable)
Check end-switch wiring for damage (where applicable)
Check damper for cleanliness and clean where necessary
Check the condition of the blades and seals, rectify and report where
necessary
Confirm the safety closure operation of the fire damper according to
the manufacturer's instructions
Confirm operation of the damper to OPEN and CLOSE by use of
physical observation of the damper, rectify and report where neces-
sary
Confirm operation of OPEN and CLOSED end-switches, rectify and
report (where necessary)
Confirm that the damper fulfills its function as part of the control sys-
tem (where necessary)
Confirm that the damper is left in its normal working position
Due to continuous product development Advanced Air (U.K.) Ltd
reserves the right to change any information without prior notice.
Burrell Way,
Thetford, Norfolk,
IP24 3QU, England
Tel: +44 (0) 1842 753624
Fax: +44 (0) 1842 762032

Maintenance Report

0160 Series
Curtain Fire Dampers
Result
Date
Issue
13/01/15
Rev 4
CE –FD Sub
Spec. No.
Page No.
14