Advanced Air AIR CONTROL 0400MAN Manual de instalación, uso y mantenimiento - Página 5
Navegue en línea o descargue pdf Manual de instalación, uso y mantenimiento para Compuertas cortafuegos y cortahumo Advanced Air AIR CONTROL 0400MAN. Advanced Air AIR CONTROL 0400MAN 11 páginas. Fire damper
FIRE – 0400MAN CIRCULAR FIRE DAMPER IN RIGID SUPPORTING CONSTRUCTION
135mm minimum thickness
two hour rated rigid supporting
construction to BS EN 1363-1:2020
Access door
0400MAN
PRODUCT
P105424-1003
CLASSIFICATION REPORT NO.
TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING.
Fire batt
Preparation
1
Ensure the that damper is kept in a clean dry
environment and that there is no damage to the
damper.
2
Work out the opening size to be cut by adding
55mm to the duct diameter and cut a square hole to
that size, see adjacent table.
Installation sequence
3
The damper should be mounted in the opening with the fixing flange (access side) flush with the wall.
4
Confirm that the blade is horizontal, and the handle is on the RH or LH. The flange can then be secured
to the wall using fire resistant steel fixings. Ensure that all the pre-drilled holes are populated.
5
The gap between the damper and the wall opening will need filling with two layers of 50mm thick
140kg/m
fire batt cut to interference fit and pushed into place. All cut edges must be sealed with a
3
fire batt sealant to BS EN 13501-2. A fire rated intumescent mastic to BS EN 13501-2 shall be applied to
each joint.
6
The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm,
leaving a 10mm clearance for any duct expansion in a fire situation.
7
The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild
steel ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at
high temperature allowing the duct to break away without affecting the integrity of the installation.
8
The connecting galvanised mild steel ductwork must be independently supported within one metre of
the connections and have been installed in accordance with DW144.
9
An access door should be fitted on the access side of the damper for inspection and maintenance.
10
When the damper installation is complete the operation of the damper should be checked.
11
Complete DW145 Fire Damper Certificate.
RIGID SUPPORTING CONSTRUCTION
APPLICATION
E120 (VE I O)
CLASSIFICATION
Nom. duct diameter
Opening size
100mm
155 x 155mm
125mm
180 x 180mm
150mm
205 x 205mm
160mm
215 x 215mm
200mm
255 x 255mm
250mm
305 x 305mm
300mm
355 x 355mm
315mm
370 x 370mm
5