5. Connection

Refer to the terminal name on the front name plate of the main unit, and connect according to the wiring
diagram below or the wiring diagram name plate on the lower side of the main unit.
Use the included M4 screws to connect the auxiliary power supply, input voltage, input current, output,
and ground terminals.
〔Applicable solderless terminal〕
Solderless terminal for M4 screw
Outer diameter of terminal, 8.5mm or less
Tightening torque:1.0 to 1.3 N・m
■ Connection diagram
● Standard:2-phase (S-phase) current measurement
1
2
3
P1
S1
AUX.SUPPLY
・By changing the wiring, 1-phase (R-phase) current
and 3-phase (T-phase) current can be measured.
・Grounding is class D grounding (grounding
resistance 100Ω or less).
・If there is a power line that causes noise or a
sharp voltage fluctuation, separate the output
wiring as much as possible. In addition, use
twisted cable or shielded twisted cable.
・This product will not be damaged even if the output terminal is left open in the current output
specifications.
・After completing the wiring work, attach the terminal cover.
Auxiliary supply terminal Output terminal
LOAD
2S
2L
P2
P3
A(+)B
(-)
S2
E
OUTPUT
S1( ), S2( ) A(+), B(-)
● 1-phase (R-phase) current measurement
1
2
3
● 3-phase (T-phase) current measurement
1
2
3
6
Input current terminal
2S, 2L
Input voltage terminal
P1, P2, P3
Ground terminal
E
2S
2L
P1
P2
P3
2S
2L
P1
P2
P3
Q-222-030
LOAD
LOAD