MOUNTING AND WIRING
Mount CT03 into a 45x45mm panel cut-out (Fig.1) and tighten it into place by the snap-on mounting bracket. Wire the timer using
OCTAL connector and strictly following the wire diagram on Fig.2. Do not turn the power supply on while mounting and wiring!
10
72
95 max
Fig.1
OPERATING
CT03 has two contact control inputs for external (re)start (START) and time-counting hold-up (HOLD). Combinations of two adjustable
time periods – t1(1
period, beginning after START) and t2 (2
st
below). The duration of each period is adjustable within one of the following five sub-ranges: 0.00...9.99 sec, 0.0...99.9 sec, 0...999 sec,
0...999 min, and 0...999 min x 10. There are two control outputs - K1, which activates alternatively with t1 and t2, and K2, which
activates for the total cycle time - whose action can be programmed with parameters
MODE 0
one-shut cycle: t1 + t2
POWER
START
HOLD
tc
rSb1=1
K1 (ACt=0)
t2+th2
rSb1=0
rSb1=1
K1 (ACt=1)
t1+th1
t2+th2
rSb1=0
ACt2=1
rSb2=1
K2
ACt2=0
rSb2=0
MODE 2
one-shut cycle (t2 - total time) : t1 + (t2-t1)
POWER
START
HOLD
tc = t2 + th1 + th2
rSb1=1
K1 (ACt=0)
t2-t1+th2
rSb1=0
rSb1=1
K1 (ACt=1)
t1+th1
t2-t1+th2
rSb1=0
ACt2=1
rSb2=1
K2
ACt2=0
rSb2=0
tc - total cycle time; th1, th2 - times when HOLD input holds time counting
+0.5
45
Fig.2
period or Total time) form 4 different timing modes (see time diagrams
nd
1,
2,
1, and
ACt
ACt
rSb
MODE 1
repeated cycle: t1, t2, t1, t2,....
POWER
START
HOLD
tc
rSb1=1
K1 (ACt=0)
t2+th2
rSb1=0
rSb1=1
K1 (ACt=1)
t1+th1
rSb1=0
t2+th2
rSb2=1
ACt2=1
K2
rSb2=0
ACt2=0
MODE 3
repeated cycle (t2 - total time) : t1, (t2-t1), t1, (t2-t1),....
POWER
START
HOLD
tc = t2 + th1 + th2
rSb1=1
K1 (ACt=0)
t2-t1+th2
rSb1=0
rSb1=1
K1 (ACt=1)
t1+th1
rSb1=0
t2-t1+th2
rSb2=1
ACt2=1
K2
ACt2=0
rSb2=0
PROGRAMMING
2.
rSb
tc
t1
t2
t1
t2
tc = t2
t1
t2-t1
t1
t2-t1