DPS Telecom Building Status Unit II Manual del usuario - Página 15

Navegue en línea o descargue pdf Manual del usuario para Sistema de seguridad DPS Telecom Building Status Unit II. DPS Telecom Building Status Unit II 20 páginas.

DPS Telecom Building Status Unit II Manual del usuario
10

Audible Notification

The NetGuardian may activate the BSU II speaker as certain conditions occur. Press the large red ACO button to
locally terminate the sound. You can also use the thumb wheel to adjust the speaker volume.
Fig. 10.1 Press the large red ACO button to terminate the audible notification.
Fig. 10.2 Use the thumb wheel to adjust the speaker volume level.
11

Operation and Troubleshooting

11.1

COMM LED Operation

The Comm LED provides quick status of bi-directional communication. On the unit, a red blink indicates data
receive, while a green blink indicates data transmitted. During normal operation, the LED will flash red/green. If
you observe a slow green blink on the BSU II, this indicates a communication failure.
Use the following steps for troubleshooting:
1. Verify addresses is correct.
2.
Verify baud rate is correct and is set to 1200.
3.
Verify wiring connections.
4.
Cycle power on BSU II and check Comm LED.
5.
Review NetGuardian System Alarm 59-61 for communication status — refer to Figure 11.1.
Similarly, data port 8 LED on the front of the NetGuardian may be used for diagnosis. You will observe a
11