(3) Remote controller address
i) 3-wire type
Rotary switch (RC AD SW)...Factory setting "0"
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting
Setting range
Remote controller
0 to 15
address
Example
If 4 indoor units are connected.
Indoor unit
Indoor unit
RC AD SW
RC AD SW
0
1
Remote
controller
RC AD SW
0
1
Address
0
1
RC AD SW
8
9
Address
8
9
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting "0"
Since the remote controller address settings are automatically confi gured, you do
not need to confi gure them.
If confi guring manually, it is necessary to confi gure both the indoor unit and the
remote controller.
For details, please refer to the remote controller manual.
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor
unit
Remote
controller
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2 referring to the Table B.
ON
OFF
SW
SW
SW
1
2
Table B
A (Factory setting)
DIP switch SET3 SW1
DIP switch SET3 SW2
En-15
Type of switch
Setting
example
0
RC AD
Indoor unit
Indoor unit
RC AD SW
RC AD SW
2
3
2
3
4
5
2
3
4
5
A
B
C
D
10
11
12
13
Code change
A
B
C
A
B
C
DIP switch "SET3"
SW
3
4
Custom code
B
OFF
ON
OFF
OFF
OFF
ON
7.3. Switching the upper limit of cooling
temperature
This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool
DIP switch setting
Set the DIP switch SET 4 SW3 referring to the Table C.
6
7
6
7
E
F
14
15
Table C
DIP switch SET 4 SW3
OFF (Factory setting)
NOTE:
Please do not make a standard setup and an extension setup intermingled in remote
controller group.
7.4. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
D
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
D
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the pip-
* Also check again to make sure no wiring mistakes were made before turning
Function details
Function
Filter
indicator
interval
Filter
indicator
action
Cool air
temperature
trigger
C
D
ON
ON
Heat air
temperature
trigger
ON
OFF
SW
SW
SW
1
2
3
Cooling temperature setting range
ON
ing air tight test and vacuuming have been conducted before turning on the
power.
on the power.
Function
Setting number
number
00
Default
01
Longer
11
02
Shorter
00
Enable
01
Disable
13
Display only
on central
02
remote
controller
00
Default
30
01
Adjust (1)
02
Adjust (2)
00
Default
01
Adjust (1)
31
02
Adjust (2)
03
Adjust (3)
DIP switch "SET4"
SW
4
Standard (18 to 30 °C)
Extension (18 to 32 °C)
Details
Default
○
Adjust the fi lter cleaning
interval notifi cation. If the
notifi cation is too early,
change to setting 01. If the
notifi cation is too late, change
to setting 02.
○
Enable or disable the fi lter
indicator. Setting 02 is for
use with a central remote
controller.
○
Adjust the cool air trigger
temperature. To lower the
trigger temperature, use
setting 01. To raise the trigger
temperature, use setting 02.
○
Adjust the heat air trigger
temperature. To lower the
trigger temperature by 6
degrees C, use setting 01. To
lower the trigger temperature
by 4 degrees C, use setting
02. To raise the trigger tem-
perature, use setting 03.