AirStage ARXD014GLEH Manual de instalación - Página 13
Navegue en línea o descargue pdf Manual de instalación para Aire acondicionado AirStage ARXD014GLEH. AirStage ARXD014GLEH 18 páginas. Indoor unit (duct type)
Tighten the terminal screws to the specifi ed torques, otherwise, abnormal overheating
may be produced and possibly cause heavy damage inside the unit.
Terminal number
M3 screw (Transmission/X1, X2)
(Remote controller/ Y1, Y2)
To peel the fi lm from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the cable by overtightening
the screw. On the other hand, an undertightened screw can cause faulty contact, which
will lead to a communication failure.
6.4. Connection of wiring
(1) Remove the cover.
(2) Connect the connection cable.
Power supply
cable
Avoid touching the ceiling with the wiring
Ceiling
Do not bind the power supply cable and other cables together.
WARNING
Tightening torque
0.5 to 0.6 N·m
(5 to 6 kgf·cm)
CAUTION
Cover
Screw
Y1,Y2: Remote
controller cable
X1, X2: Transmission cable
GND
L, N: Power supply cable
Cable clamp
Cable tie (Medium)
(Accessories)
Avoid covering the air
inlet with the wiring.
6.5. Optional parts wiring
6.5.1. Layout of the indoor unit PCB
CN820
CN155
Power indicator
lamp (green)
CN8
CNA04
CNA02
CNA03
Name
Power indicator
Indicates the state of the power supply. Refer to "Power indicator
lamp (green)
lamp status" following.
CN150
Connect to the Grille. (*1)
CN151
CN152
CNA01
Apply voltage terminal
CNA03
CNA02
Dry contact terminal
CNA04
DIP switch SET 2
Input signal type switching
(SW2)
CNB01
Output terminal
CN8
For Remote sensor unit (*1)
CN48
For IR receiver unit (*1)
CN65
For one of the following.
• MODBUS® convertor (*1)
• Wireless LAN adapter (*1)
CN155
For Auto louver grille kit (*1)
CN820
For External power supply unit (*1)
*1: For details, refer to each installation manual.
6.5.2. Power indicator lamp status
Power indicator lamp (Green)
Lit
Lit when the power is turned on.
There is a fault with the communication board or the
Fast flashing (every 0.1
second)
main board.
The indoor unit is turned off and power is supplied
Blinking (repeat 3 seconds ON
from the External power supply unit (optional) to the
and 1 second OFF)
indoor unit PCB.
6.4.2 Connection methods
Wire modification for External
input/output wire
(1) Remove insulation from wire at-
tached to wire kit connector.
(2) Remove insulation from field
supplied cable. Use crimp type
insulated butt connector to join field
cable and wire kit wire.
(3) Connect the wire with connecting
wire with solder.
CN65
Controller PCB
DIP switch
(SET 2)
CN48
CNB01
CNA01
Application
For external input
For external outnput
Status contents
IMPORTANT:
Be sure to insulate the connection between the
wires.
Locally
Wire kit connector
purchased
(optional parts)
Solder and insulate the connected parts.
En-12