AirStage ASUA14RLAV Manual de instalación - Página 10
Navegue en línea o descargue pdf Manual de instalación para Aire acondicionado AirStage ASUA14RLAV. AirStage ASUA14RLAV 15 páginas. Indoor unit (wall mounted type)
Setting
Setting
range
Remote controller
0–15
address
Example If 4 indoor units are connected.
Indoor unit
Indoor unit
RC AD SW
RC AD SW
0
1
Remote
controller
RC AD SW
0
1
Address
0
1
RC AD SW
8
9
Address
8
9
6.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor
unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP SW SET 3 SW1, SW2 referring to the Table B.
ON
OFF
Dip switch
"SET 3"
Table B
A (Factory setting)
DIP SW SET 3 SW1
DIP SW SET 3 SW2
6.3. Function Setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "6.1. Setting the address." for indoor unit address and refrigerant circuit ad-
dress settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
En-9
Type of switch
Setting
example
0
RC-AD
Indoor unit
Indoor unit
RC AD SW
RC AD SW
2
3
2
3
4
5
2
3
4
5
A
B
C
D
10
11
12
13
Code change
A
B
C
D
A
B
C
D
Custom code
B
C
OFF
ON
OFF
OFF
OFF
ON
Function details
Function
Function
number
Filter
indicator
11
interval
Filter indi-
13
cator action
Cool air
tempera-
30
ture trigger
6
7
6
7
Heat air
tempera-
31
E
F
ture trigger
14
15
Auto restart
40
External
46
control
Error report
47
target
6.3.1 Button name and function
D
ON
ON
OPERATION indicator lamp (Green)
6.3.2 Checking the function settings
Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check the
function settings. It is necessary to disconnect the power in order to return to normal op-
eration mode.
Setting number Default
○
00
Default
Adjust the fi lter cleaning interval notifi ca-
tion. If the notifi cation is too early, change
01
Longer
to setting 01. If the notifi cation is too late,
change to setting 02.
02
Shorter
○
00
Enable
01
Disable
Enable or disable the fi lter indicator.
Setting 02 is for use with a central
Display only
remote controller.
on central
02
remote
controller
○
00
Default
Adjust the cool air trigger temperature. To
lower the trigger temperature, use setting
01
Adjust (1)
01. To raise the trigger temperature, use
setting 02.
02
Adjust (2)
○
00
Default
Adjust the heat air trigger temperature. To
lower the trigger temperature by 11 degrees F
01
Adjust (1)
(6 degrees C), use setting 01. To lower the
trigger temperature by 7 degrees F
02
Adjust (2)
(4 degrees C), use setting 02. To raise the
trigger temperature, use setting 03.
03
Adjust (3)
00
Enable
Enable or disable automatic
system restart after a power
○
01
Disable
outage.
○
Allow an external controller to start or stop
00
Start/Stop
the system, or to perform an emergency stop.
Emergency
* If an emergency stop is performed from an
01
stop
external controller, all refrigerant systems
will be disabled.
* If forced stop is set, indoor unit stops by
Forced
the input to the external input terminals,
02
stop
and Start/Stop by a remote controller is
restricted.
○
00
All
Change the target for reporting errors. Er-
Display only
rors can either be reported in all locations,
on central
01
or only on the wired remote.
remote
controller
FILTER indicator lamp (Red)
TIMER indicator lamp (Orange)
Details