AirStage AUXK030GLAH Manual de instalación - Página 12

Navegue en línea o descargue pdf Manual de instalación para Aire acondicionado AirStage AUXK030GLAH. AirStage AUXK030GLAH 13 páginas. Indoor unit (cassette type)

7.3. Function setting

• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number
number
00 Standard
Filter indica-
11
01 Longer
tor interval
02 Shorter
00 Enable
01 Disable
Filter indica-
13
Display only
tor action
on central
02
remote
controller
00 Standard
Ceiling
20
airflow
01 High Ceiling
Vertical
00 Standard
airflow
23
direction
01 Adjust
00 Standard
Cool air
temperature
30
01 Adjust (1)
trigger
02 Adjust (2)
00 Standard
Heat air
01 Adjust (1)
temperature
31
02 Adjust (2)
trigger
03 Adjust (3)
00 Enable
Auto restart
40
01 Disable
00 Super low
Cool Air
Follow the
43
Prevention
setting on
01
the remote
controller
00 Start/Stop
Emergency
01
stop
External
46
control
02 Forced stop
00 All
Error report
Display only
47
target
on central
01
remote
controller
Follow the
Fan set-
setting on
00
ting when
the remote
cooling
49
controller
thermostat
OFF
01 Stop
(Forbidden)
60
00
(Forbidden)
61
00
En-11
Default
Details
Adjust the filter cleaning interval
notification. If the notification
is too early, change to setting
01. If the notification is too late,
change to setting 02.
Enable or disable the filter indi-
cator. Setting 02 is for use with a
central remote controller.
Regulate the airflow according
to the needs of the installation
location. When set to 01, the air
flow will be stronger. (Cassette
type only)
Adjust the vertical airflow direc-
tion. All airflow direction louvers
are adjusted together.
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature,
use setting 02.
Adjust the heat air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
Enable or disable automatic
system restart after a power
outage.
Restrain the cold airflow with
making the airflow lower when
starting heating operation. To
correspond to the ventilation,
set to 01.
Allow an external controller to
start or stop the system, or to
perform an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant
systems will be disabled.
* If forced stop is set, indoor
unit stops by the input to the
external input terminals, and
Start/Stop by a remote control-
ler is restricted.
Change the target for reporting
errors. Errors can either be re-
ported in all locations, or only on
the central remote controller.
When set to 01, the fan stops
when the thermostat is OFF in
cooling operation. Connection
of the wired remote control-
ler (2-wire type or 3-wire type)
and switching its thermistor are
necessary.
Function
Function
Setting number
number
(Forbidden)
62
00
Single
setpoint auto
00
mode
Auto mode
68
(traditional)
type
Dual setpoint
01
auto mode
00 0°C
01 0.5°C
02 1.0°C
03 1.5°C
04 2.0°C
Deadband
69
value
05 2.5°C
06 3.0°C
07 3.5°C
08 4.0°C
09 4.5°C

8. CASSETTE GRILLE INSTALLATION

• Operate according to the installation Manual CASSETTE GRILLE.
• Be sure to confirm there is no gap between the cassette grille and main unit after install-
ing the CASSETTE GRILLE.

9. TEST RUN

9.1. Test run using Outdoor unit (PCB)

Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to be
used for the test run.

9.2. Test run using remote controller

• Refer to the Installation Manual for the remote controller to perform the test run using the
remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamp
flash slowly at the same time.

10. CHECK LIST

Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
Check items
Has the indoor unit been installed
correctly?
Has there been a check for gas leaks
(refrigerant pipes)?
Has heat insulation work been com-
pleted?
Does water drain easily from the indoor
units?
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
Are the wires and pipes all connected
completely?
Is the indoor unit earthed (grounded)?
Is the connection cable the specified
thickness?
Are the inlets and outlets free of any
obstacles?
Does start and stop air conditioner
operation by remote control unit or
external device?
After installation is completed, has the
proper operation and handling been
explained to the user?
Default
Details
Switch the setting method of
auto mode to single or dual
(cooling/heating).
For heat pump systems, it is
necessary to set the master
indoor unit (by wired remote
controller).
Choose the minimum temperature
between cooling and heating
settings (deadband) for Dual
setpoint auto mode (set in No. 68).
If not performed correctly
Vibration, noise, indoor unit may
drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or burn damage
No operation, heat or burn damage
Short circuit
No operation, heat or burn damage
No cooling, No heating
No operation
Check
box