AirStage UTY-DCGG Manual de instalación - Página 5

Navegue en línea o descargue pdf Manual de instalación para Mando a distancia AirStage UTY-DCGG. AirStage UTY-DCGG 11 páginas. Central remote controller
También para AirStage UTY-DCGG: Manual de instalación (9 páginas)

WARNING
When connecting the power supply cable and trans-
mission cable, layout the wiring so that the cover of
this unit is securely fixed. If the cover is imperfectly
fixed, it may cause fire or overheating of the terminals.
Perform earth (ground) work positively. Do not connect
the earth (ground) cable to a telephone earth (ground)
cable, water pipe, or conductor rod. It will cause
trouble or fire.
Always fasten the outside covering of the cable with
binder. If the insulator is chafed by friction, electric
leakage may occur.
If any cable is damaged, do not repair or modify it
yourself. Improper work will cause electric shock or
fire.
CAUTION
Do not bind up the power supply cable together with
the transmission cable or remote controller cable. It
will cause erroneous operation.
When performing wiring work, be careful not to dam-
age the cable or injure yourself. Also, connect the con-
nectors securely. loose connectors will cause trouble,
heating, fire, or electric shock.
Install the indoor and outdoor units, power supply
cable, transmission cable and remote controller cable
1m (40 in.) away from television and radio to avoid
distorted images and noise. Otherwise, a malfunction
could result.
Perform wiring so that water does not enter this unit
along the external wiring. Always install a trap to the
wiring or take other countermeasures. Otherwise it will
cause trouble, electric shock, or fire.
Confirm the name of each unit and name of each
terminal block of the unit and connect the wiring in
accordance with the directions given in the manual so
that there is no incorrect wiring. Incorrect wiring will
damage the electric parts and cause smoke and fire.
When installing the connection cables near a source
of electromagnetic waves, use shielded cable.
Otherwise,a breakdown or malfunction could result.
When wiring between the outdoor unit, indoor unit, and
Central remote controller, refer to the indoor unit and
outdoor unit installation manuals.
Always connect both ends of the earth (ground) con-
nection of the transmission cable.
Install the disconnect switch to the easily accessible
location.
Install the fuse (5A) to the l line of power supply cable.
Power
Transmission
supply
X1 X2
Z1 Z2
H1 H2
Outdoor unit
(Master)
Transmission
Power
Power
Indoor unit
supply
supply
Power
Trans-
Remote
Supply
mission
controller
L N
X1 X2
Y1Y2Y3
Wired remote
controller
Power
Power
supply
Indoor unit
supply
Power
Trans-
Remote
Supply
mission
controller
L N
X1 X2
Y1Y2Y3
Central remote
controller
Power
Trans-
Supply
mission
L N
X1 X2
2 remote
controllers
Fuse (5A)
1Ø 50/60Hz
100-240V
Switch
(Disconnect switch)
Wire the transmission cable to any one of the following:
Transmission terminal block inside the indoor unit
(Fig. 1)
Terminal block for branch Transmission cable (Pro-
cured at the site) (Fig. 2)
Transmission terminal block inside the outdoor unit
(Fig. 3)
Fig1
1
Refrigerant
system 1
Refrigerant
system 2
1Ø 50/60Hz
100-240V
Central remote
controller
Switch
Power
Trans-
(Disconnect
Supply
mission
L N
X1 X2
switch)
Fuse (5A)
Power
Indoor unit
Indoor unit
supply
Power
Trans-
Remote
Power
Trans-
Remote
Supply
mission
controller
Supply
mission
controller
L N
X1 X2
Y1Y2Y3
L N
X1 X2
Y1Y2Y3
Wired remote
controller
Power
Indoor unit
supply
Indoor unit
Power
Trans-
Remote
Power
Trans-
Remote
Supply
mission
controller
Supply
mission
controller
L N
X1 X2
Y1Y2Y3
L N
X1 X2
Y1Y2Y3
Wireless
remote
controller
2 remote
controllers
Central remote
controller
En-4