6.
INSTALLATION METHOD
6. 1.
Selecting the Method of Installation
The following are the 2 methods for installing the central remote
controller based upon the installation method of the control unit and
power supply unit.
A. Control unit and power supply unit together (Fig. A)
B. Control unit and power supply unit separately (Fig. B )
Fig.
A
Fig.
B
6. 2.
6. 2. 1
(1)
(2)
Central remote
controller
(3)
6. 2. 2
(1)
(2)
6. 3.
Use an insulated screwdriver to set the DIP switches. Do not touch
the DIP switch with your hands.
▪
Before using this product, always set DIP switch (SW1)-No.1 to
"ON".
If not set, when the main power is turned on again, the set data by
menu operation will be erased and cause erroneous operation.
▪
Do not change the setting of other switches.
[DIP Switch(SW1)]
▪
Performs the enabling/disabling of the backup function by the inter-
nal battery.
▪
It is disabled when shipped from the factory to prevent consumption
of the charge.
Preparing Installation
Controller unit
Remove the screw (1 pc).
Remove the claws (2 places) with a fl at-blade screwdriver, and
separate the front panel and rear panel.
Claws
Screwdriver
Disconnect the connection cable connector from the connector
(CN13) of the front panel PC board.
Front panel
CN13
Connection cable
Power supply unit
Remove the screws (4pcs).
Remove the cover.
cover
DIP Switch Setting
CAUTION
DIP Switch (SW1)
Front panel
Rear panel
Rear panel
ON
OFF
1 2 3
En-4