Carlin 60200 Manual - Página 2
Navegue en línea o descargue pdf Manual para Sistemas de control Carlin 60200. Carlin 60200 4 páginas. Cad cell oil primary control

Wiring
Startup & Operation
Power ON
Open all manual oil line valves. Close the line switch. (If Red LED turns on constant
out. See next page to reset.)
Self-test 1
The control performs a "boot-up" test to verify internal operation each time power is applied to the L1 wire.
The amber LED turns on and the test continues for about 5 seconds. If the test fails, the control turns the
amber LED off and repeats this test sequence until successful.
Stand-by
(No call for heat) If Self-test 1 is successful, amber LED turns off and control waits for heat call.
Call for
Set thermostat to call for heat. Thermostat circuit must be closed and black wire must receive
heat
power from the limit circuit.
Self-test 2
If a failure occurs in this self-check, the control won't start and the amber LED blinks 1 second on, 4
seconds off, until serviced or the problem clears. These failures include CAD cell seeing light, valve lead
voltage on too early, internal fault, or line voltage <90 V. See service section.
Burner on
After the self-test, amber LED turns off. The ignitor starts, followed 2 seconds later by the motor.
Valve delay
The oil valve opens after the valve delay-on period (pre-purge). (For oil valve delay on operation, wire oil
ON
valve to the violet lead. If not using an oil valve, cap the violet lead to automatically disable pre-purge and
post-purge).
Pump
To enter pump prime: 1. Start a CFH cycle. During Pre-Ignition or Valve Delay On, press Reset until motor
Prime
turns off (10 seconds), then release the button. When motor turns back on, within 5 seconds, press the Reset
button until the amber LED starts to flash. You are in Pump Prime, release Reset button.
Optional Pump Prime notes: 1) If lost, press Reset for 1 second and release, then if the control is not in
Pump Prime, restart the sequence. 2) If Reset is released before end of first 10 seconds, the control re-
turns to Standby and restarts another CFH cycle. 3) If reset is not pressed the second time, a normal CFH
cycle will continue. 4) If motor and igniter are on and amber LED is flashing, the control is in Pump Prime.
5) Pump Prime will exit standby if flame is detected, or 60 seconds has elapsed, or loss of TT or Limit, or
Reset button is pressed.
© Copyright 2015 - Carlin Combustion Technology, Inc.
(continued)
, control is in lock-
MN60200G 022415