ECONO Mode Prohibition Setting

WARNING
Always shut off the power supply breaker before starting.
• This setting disables the input control signal from the remote controller.
• Use this setting when you wish to block reception of input controls (cooling/heating) from indoor unit remote controllers.
• Set as follows.
1) Remove the two screws on the side and remove the top plate of the outdoor unit.
2) Remove one screw from the upper electric box cover.
3) Remove the upper electric box cover by sliding it, being careful not to bend the electric box hook.
4) Remove the lower electric box cover.
5) Cut the jumper (J3) of the PCB inside.
6) Go back through step 4) → 3) → 2) → 1). Make sure all components are well secured when doing this.
1) Remove the
two screws.
Fan motor lead wire
Hook
3) Remove the upper
electric box cover
from the hook.
CAUTION
• When removing the upper electric box cover, be careful not to bend the hook.
• When returning the lower electric box cover, return the notch to the stop valve side.
• When returning the upper electric box cover, be careful not to pinch the fan motor lead wire.
13
Upper electric
box cover
Lower electric
box cover
Top plate
PCB
5) Cut jumper J3.
2) Remove the
one screw.
4) Remove the lower
electric box cover.
Notch
Electric box
PCB