Daikin Altherma 3 H HT EPRA16DAW1 Manual de instalación - Página 13
Navegue en línea o descargue pdf Manual de instalación para Bomba de calor Daikin Altherma 3 H HT EPRA16DAW1. Daikin Altherma 3 H HT EPRA16DAW1 20 páginas.
También para Daikin Altherma 3 H HT EPRA16DAW1: Manual de instalación (20 páginas)
1
2
3
3 (Optional) Drain tube heater cable:
▪ Make sure the heating element of the drain tube heater is
completely inside the drain tube.
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block and the earth screw.
▪ Fix the cable with cable ties.
Wires: (2+GND)×0.75 mm². Wiring must be double insulated.
Maximum power allowed for drain tube heater = 115 W (0.5 A)
—
EPRA14~18DAV3+W1
Daikin Altherma 3 H HT
4P586100-1B – 2019.09
1 2 3
5.4
This procedure is only necessary in areas with low ambient
temperatures.
Required accessory (delivered with the unit):
2
4
6
5 Electrical installation
1 2
To reposition the air thermistor on
the outdoor unit
Thermistor fixture.
1
3
5
7
Click
Installation manual
13