Setting the nominal air quantity

Warning: Serious personal injury may result from improper working procedures. The
nominal air quantity may only be set by suitably qualifi ed and authorised technicians.
Before setting the nominal air quantity, the unit must be fully disconnected from the
mains.
Open the latches for the inspection doors at the top of the unit.
Remove the cover guard from the controller unit (a) using a suitable Phillips screwdriver.
The nominal air quantity for the unit is set using DIP switches 5 to 8 on the controller board.
Controller board:
Page 16
A) FSH switching point
B) DIP switch
C) Room operating panel
D) Total error