The AeroLogic
Air Duct Disinfection Unit comes standard with a 1-inch Sight Glass Assembly, which is installed
separately. The ultraviolet blocking, sight glass allows for visual inspection of the lamps, without the need to remove
the unit from the duct.
1. Select a suitable location near the AeroLogic
2.
Using the Sight Glass Mounting Cutout (See Figure 6 on page 9) mark the centers of the mounting holes and
clearance hole for the sight glass.
!
CAUTION:
Wear protective gloves when working on or around duct sheet metal.
3.
Cut out the opening for the sight glass. Remove burrs and sharp edges where possible.
4.
Using the supplied No. 8-18 x 3/8" long hardware, mount the sight glass assembly to the duct.
8
- S
G
ATA
IGHT
LASS
Figure 3 - Sight Glass Dimensional Data
& I
OCATION
NSTALLATION
Mechanical hazard. Duct sheet metal has sharp edges.
®
installation.