Bose FreeSpace DS 100SE Manual de instalación - Página 21
Navegue en línea o descargue pdf Manual de instalación para Altavoces Bose FreeSpace DS 100SE. Bose FreeSpace DS 100SE 22 páginas. With ceiling mount bracket
También para Bose FreeSpace DS 100SE: Manual del usuario (32 páginas), Manual de instalación (17 páginas), Ficha técnica (8 páginas), Manual de diseño (4 páginas), Manual de servicio (21 páginas)
The DS 40SE has passed extensive testing and complies with the following specifications and uses:
• LISTED to ANSI/UL 1480-2005
• Fire Protective Signaling Use – UL Category UUMW, File Number S 3241.
Control Number 42S9 when installed with a ceiling mount bracket.
Not for use with DC-supervised systems.
• General-Purpose Use – UL Category UEAY, File Number S 5591 Control Number 3N89.
• Suitable for use outdoors in wet locations.
• Suitable for installation using Class 1, Class 2, or Class 3 wiring methods in accordance with NFPA 70, National Electric Code, 2008,
Article 640.
• Suitable for use with fire alarm circuit wiring methods in accordance with NFPA 70, National Electric Code, 2008, Article 760.
• The DS 40SE has been designed to the requirements defined in the following European regulatory specification for combination systems:
• British Standard Code of Practice BS 5839, Part 8.
UL Sensitivity Wattage Tap Sound Pressure Level dBA at 3.1 meters (10 feet):
Wattage
ANSI/UL 1480-2005
Tap
70V
2.5 Watt
81 dBA
5 Watt
84 dBA
10 Watt
87 dBA
20 Watt
89 dBA
40 Watt
92 dBA
8 Ohm
91 dBA
SPLs given are per the UL 1480 specified reporting method.
Frequency response:
Fire alarm: 400 Hz to 4 kHz
General signaling: 80 Hz to 16 kHz (±3dB)
Wire gauge
The FreeSpace
®
DS 40SE loudspeaker bracket is designed to work with 18 AWG (0.8 mm
Safety and Regulatory Compliance
100V
84 dBA
86 dBA
89 dBA
92 dBA
2
) to 14 AWG (2.0 mm
2
) size wire only.
21