6.1 Troubleshooting (continued)
Please use caution when troubleshooting or repairing all electrical components. Be certain that
all power is disconnected from the COOL-SPACE
are removed to gain access to the fan.
Problem
Fan won't run and makes no
sound.
Fan motor won't run and makes
a humming sound.
Breaker trips or fuse blows when
fan is started.
Motor overheating and shutting
off. Restarting several minutes
later.
Fan motor won't run and switch
makes soft clicking sound.
Fan blade doesn't turn and unit
makes squealing sound.
Fan belts do not last very long.
Fan will not reach speed but
turns and makes humming
sound.
Fan System
®
unit before the cooling pads or fan guard
Direct & Belt Drive Models
Check
Power cord, extension cord,
switches, circuit breaker, GFI
ground fault.
Blade in contact with shroud.
Motor stalled (will not turn by
hand).
Motor stall.
Check power source for min.
220v/10 amp. Extension cord.
Extension cord gauge too small
Inlet air obstructed or too
close to wall
Faulty motor
Loose belt
Switch making good contact.
Motor stall (as above). Fan
belt loose or broken.
Fan pulley spinning on shaft.
Motor and fan pulleys alignment.
Capacitor (where visible) and
motor electrical connections.
Extension cord to small.
7
Solution
Reconnect power or extension
cord. Reset breaker.
Re-center blade hub.
Replace motor.
Replace motor.
Upgrade power supply.
Replace with heavier cord.
Replace with heavier cord
Provide minimum 1 metre
inlet clearance.
Replace motor.
Tighten belt
Replace switch.
Replace motor.
Tighten or replace fan belt.
Tighten pulley set screw.
Realign motor and fan pulleys.
Replace capacitor or motor.
Increase cord gauge.