Beckett 7575P054M Manual - Página 9

Navegue en línea o descargue pdf Manual para Controlador Beckett 7575P054M. Beckett 7575P054M 12 páginas. 120v advanced burner control

Beckett 7575P054M Manual

Sequence of Operation

Burner States

1. Standby: The burner is idle,
waiting for a call for heat.
2. Valve-On Delay: The igniter and
motor are on while the control
delays turning on the oil solenoid
valve for the programmed time.
3. Trial For Ignition: The oil solenoid
valve is energized. A flame should
be established within the factory
set trial for ignition time ("lockout
time").
4. Lockout: The control has shut
down for one of the following safety
reasons:
a. The trial for ignition (lockout)
time expired without flame being
established.
b. The cad cell detected flame at the
end of the Valve On Delay state.
c. Flame is lost while the burner
is firing and the pre-set time
allotment is expired. See
"Recycle" (Item 7).
To reset the control from lockout
click the button 1-second.
NOTE: A recurrence of the above
failure modes or a failed welded
relay check could cause the control
to enter a Hard Lockout state that
must be reset only by a qualified
service technician.
To reset from Hard Lockout, hold the
reset button for 15 seconds until the
yellow light turns on.
5. Ignition Carryover: Once flame is
established, the igniter remains on
for 10 additional seconds to ensure
flame stability.
6. Run: The flame is sustained until the
call for heat is satisfied. The burner
120v GeniSys Control Installation and Operation Manual
1
Standby
3
2
Trial for
Valve-on
ignition
delay
5
Ignition
carryover
6
8
Motor-off
delay
is then sent to Motor-Off Delay, if
applicable, or it is shut down and
sent to Standby.
7. Recycle: If the flame is lost while
the burner is firing, the control shuts
down the burner, enters a 60 second
recycle delay, and repeats the
ignition sequence. The control will
continue to Recycle each time the
flame is lost, until it reaches a pre-set
time allotment. The control will then
go into Lockout instead of recycle.
This feature prevents excessive
accumulation of oil in the appliance
firing chamber.
8. Motor-Off Delay: If applicable, the
oil solenoid valve is turned off and
the control delays turning the motor
off for the set motor-off delay time
before the control returns to standby.
9. Pump Prime: The igniter and motor
are on with the oil solenoid valve
energized for 4 minutes. During
Pump Prime mode, the cad cell is
disregarded, allowing the technician
to prime the pump without having to
jumper the cad cell.

Reset Button Operation

Table 2 explains what action the control
will take when the reset button is pressed
for different lengths of time during the
various burner operating states.
9
Pump
prime
4
Lockout
7
Recycle
Run
9