Fox-Lux FXD02 Manual de inicio rápido

Navegue en línea o descargue pdf Manual de inicio rápido para Equipos de iluminación Fox-Lux FXD02. Fox-Lux FXD02 2 páginas. Led emergency downlight

FXD02 LED EMERGENCY DOWNLIGHT
Thank you for purchasing our FXD02 LED Emergency Downlight.
Our products have been designed according to the relevant standards. If installed and maintained
correctly they will provide a long service life.
BS EN 60598-1 / BS EN 60598-2-22 / BS EN 50172 / BS EN 1838 / BS EN 62034 / ISO 7010 / ISO 3864
Installation, Maintenance and Servicing Notes
• Ensure that the mains supply is switched off before installing, maintaining or servicing the luminaire.
• Luminaires should only be installed by qualified personnel.
• The LED light source and control gear are non-replaceable. Once end-of-life is reached, the
luminaire should be replaced.
• In case of mains supply failure, the battery will automatically energise the emergency light for a
minimum 3hr period. After 3hrs 5m the luminaire will enter standby
mode to protect the battery from over-discharge. The battery must be
recharged within 6 months of full discharge.
• Self-test emergency luminaires are programmed to carry out
functional and full duration tests according to BS EN 50172:2004.
• First battery charge will take up to 16hrs.
• Battery re-charge takes up to 8hrs. Note that full cycle (discharge and
recharge) takes up to 12hrs.
• Contact Fox Lux if a replacement
battery is required.
• Warranty terms apply. See website for details.
TESTING
Standard
Self-test
LED Status Indications
GREEN LED
RED LED
Solid ON
OFF
Normal Flash
OFF
OFF
Solid ON
Fast Flash
OFF
Normal Flash
Normal Flash
OFF
Normal Flash
Normal flash = 1Hz (once/second)
Fast flash = 2Hz (twice/second)
3 hour
30
40
Testing and commissioning must be carried out manually according to BS EN 50172:2004.
Functional
test is carried out automatically once a week and runs for 30s. Full duration test is carried
out automatically every 52 weeks. First full duration test is carried out automatically within the first
4 weeks after the luminaire being connected to mains.
This luminaire can be used with the optional Remote Control (REM10) which adds extra features to
Fox Lux emergency luminaires. Please refer to the REM10 user g uide.
Green Red
STATUS
OK
Charging
Battery disconnected /
Duration test failure
Functional/Duration test in progress
Battery temperature
Light source fault
IP
IP
54
20
Back & LED driver
Front
t | +44(0)1543 396400 | e | [email protected] | w | www.fox-lux.co.uk
Registered Office: Alex House 260/8 Chapel Street, Salford, Manchester, M3 5JZ
Company Registration No. 11821284 VAT Registration No. 320 9921 12
Self
Test
230
Warning: never put this luminaire inside its box
when it is in emergency mode. The luminaire can
get damaged due to heat not being able to
escape. To avoid this please disconnect and re-
connect the battery before putting the luminaire
back in the box.
ACTION REQUIRED
Connect battery /
Replace battery
Contact Fox Lux
Replace luminaire
Ensure this product is disposed
responsibly according to WEEE
directive 2002/96/EC
25