Daintree GE Current WOS2-RM Manual de instalación - Página 3

Navegue en línea o descargue pdf Manual de instalación para Accesorios Daintree GE Current WOS2-RM. Daintree GE Current WOS2-RM 5 páginas. Wireless occupancy sensor, recess mount

Daintree GE Current WOS2-RM Manual de instalación
Daintree
Wireless Occupancy Sensor, Recess Mount (WOS2-RM)
®
3
PIR Sensitivity Adjustments
TA trimpot next to the battery compartment is used to
adjust the PIR motion sensor sensitivity.
Use caution when adjusting the trimpots.
• Do not use excess force, as this will damage the unit.
• Stop turning the trimpot when you feel resistance.
4

Sensor Placement

The PIR sensor can only be installed indoors. It is extremely
important to select the appropriate installation location to
avoid false occupancy reporting while obtaining the best
sensitivity. A proper installation should meet the following
conditions:
• The PIR sensor is typically mounted 6.5' to 10' (2m to 3m)
from the floor. The height affects the coverage area.
• The PIR sensor must be 4' to 6' away from hot or cold sources
such as heat or air conditioner vents, refrigerators, stoves, etc.
The PIR sensor should not be installed in places with
strong airflows.
• The PIR sensor must have clear line of sight to the coverage area.
It may not detect a human body if it is blocked by furniture,
fixtures, large plants, glass, curtains, etc.
Coverage Pattern, WOS2-RM-S, Standard Coverage
Installation Height
10' (3m) from floor
Detection Angle
100°
Detection Radius
up to 13' (3.9m)
Clockwise to increase
sensitivity
Counter-Clockwise to
decrease sensitivity
Minimum
Maximum
(counter-
(clockwise)
clockwise)
3
Coverage Pattern, WOS2-CM-E, Extended Coverage
Installation Height
10' (3m) from floor
Detection Angle
120°
Detection Radius
up to 17' (5.2m)
Installation Guide