Ansell AG8/3NM Instrucciones de instalación
Navegue en línea o descargue pdf Instrucciones de instalación para Equipos de iluminación Ansell AG8/3NM. Ansell AG8/3NM 2 páginas. Ip20 8w guardsman emergency exit sign maintained / non maintained
General Installation Instructions
These instructions should be read carefully prior to any installation and retained after completion for further
reference and maintenance. Please give these instructions to the building owner/occupier after installation.
Important Safety
1.
Before installation, maintenance or lamp replacement, ensure that the mains supply to the luminaire is switched off and the circuit supply fuses are removed or
the circuit breaker is turned off.
2.
It is recommended that only a qualified electrical contractor carries out the installation of this luminaire and that the luminaire is installed in compliance with the
current edition of the IEE Wiring Regulations.
3.
The person carrying out the installation is to check and verify that the total load on the circuit, including that of this luminaire does not exceed the rating of the
circuit cable, fuse or circuit breaker.
4.
Where a luminaire incorporates discharge control gear (inductive load), the circuit capacity and ratings require careful sizing to avoid nuisance tripping of the
protective device used in the installation.
5.
Where applicable, careful consideration should be taken during installation to ensure that all fixings and/or suspensions are of a suitable size for the luminaire
being installed.
Ratings
1. All luminaires are manufactured & tested in compliance with the requirement contained within BS EN 60598 and are CE marked.
2. All luminaires that are of Class 1 construction and that are marked accordingly, MUST be earthed.
3. All luminaires are designed to operate at 230Volts AC -6%/+10% = 216Volts to 252Volts. Do not operate outside these voltages.
4. All luminaires are only suitable for applications within their rated Ingress Protection limits as stated.
5. Max Ambient Temperature 25
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
INSTALLATION
• Remove the luminaire end bracket by removing the screws with a screwdriver.
• Fix the base to the required surface ensuring an appropriate fixing method is used to support the luminaire.
• Bring in the incoming supply through the base and terminate into the terminal block on the gear tray.
Connect as follows:-
• Connect the battery lead to the PCB board.
• Insert desired legend into the runners of the housing.
• Refit the end bracket and replace the two fixing screws.
• Switch on the mains supply. Check the unit operates correctly.
• Check the LED indicator is ON.
• Leave the unit on charge for one hour, then remove the supply to simulate mains failure and check the lamp
operates in emergency
mode.
• The unit requires 24 hours to fully charge the battery and achieve 3 hours emergency operation.
MAINTENANCE
Daily :
Monthly :
Annually:
If the unit fails to provide the required duration, replace the battery with one that meets the same specification.
Warning
Disconnect the mains supply and unplug the battery leads before working on the unit.
•
Failure to comply with these instructions may result in irreparable damage to the emergency control gear.
•
This product must not be modified in any way as this will negate any Safety approvals, and may render the
•
product inoperable or unsafe. The product must be installed in accordance with the instructions.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Page No. 1
Description – IP20 8W Guardsman Emergency Exit Sign
Installation Instructions
Luminaire Code(s) –
o
C
PERMANENT LIVE (L)
SWITCHED LIVE
NEUTRAL
EARTH
Check LED indicator is illuminated. If the product is maintained check the lamps operate.
Check the unit operates in emergency mode for ¼ of the rated duration.
Check the unit operates of 1 hour for the 3 hour duration.
Maintained / Non Maintained
AG8/3M, AG8/3NM
(L1)
(N)
(E)
www.anselluk.com
BROWN OR RED
BROWN OR RED
(switched)
BLUE OR BLACK
GREEN / YELLOW
Issue Date: td 20140124
(continuous)