NEO HS2016 / HS2032 / HS2064 / HS20128 v1.3
Zone Attributes
The following information describes the zone attribute programming options. To modify the zone
attributes, first enter into Section [002] and then enter into the SubSection {001 – 128} (the 3
digit zone number.) After modifying the zone attributes as needed, press the # key and enter the
next zone number (SubSection) if additional zones need to be modified; or the # key a second
time to your solid red light.
Section [002] – Zone Attributes
Zone attributes are used to customize the operation of the independent zones. When a zone
type (Section [001]) is programmed, the default zone attribute is automatically assigned. See
the Reference Manual for the default attribute settings for each zone type.
Note: These attributes allow you to override the default settings. DO NOT change any fire zone
attributes from their default settings.
SubSection {001 – 128}
Note: The attributes listed below can be enabled and disabled for each zone independently.
01 – Bell Audible
ON: An alarm activates the siren.
OFF: Silent alarm.
02 – Bell Steady
ON: Siren output is steady when in alarm.
OFF: Siren output pulses when in alarm.
03 – Door Chime
ON: The keypad chimes when the zone is open and/or when the zone is secured.
OFF: The zone does not chime.
04 – Bypass Enabled
ON: The zone can be manually bypassed.
OFF: The zone cannot be bypassed.
Note: Bypass shall not be enabled for fire zones.
05 – Force Arm
ON: The system can be armed with the zone open. The zone is temporarily bypassed,
and when secured, is monitored by the system.
OFF: The system cannot be armed if the zone is open.
NEO – Zone Attributes
1 of 2
April 2018