2. Time-stamped historical events: This function shall time-stamp and store all im-
portant status changes, anomalies and faults and make this information available for
automatic or user-requested consultation; it shall interpret the events and indicate
remedial measures if applicable.
3. DB-9 RS232 Connector: One DB-9 connector with serial output will be provided for
field diagnostic actions.
4. Dry Contacts (Optional): The UPS shall be capable of providing optional relay
contacts. The contacts will be a form "C" contact and will change state to indicate the
operating status. The contacts will be rated at 2.0 A (125 VAC / 30 VDC). Contacts
shall be programmed as:
a. UPS on Line
b. Load on Bypass
c. UPS on Battery
2.6 MECHANICAL DESIGN AND VENTILATION
A. Enclosure: The UPS shall be housed in a freestanding enclosure. The mechanical struc-
ture of the UPS shall be sufficiently strong and rigid to withstand handling and installation
operations without risk. Access to UPS subassemblies shall be through the front only. The
sheet-metal elements in the structure shall be protected against corrosion by a suitable
treatment, such as zinc electroplating, powder coating, epoxy paint or an equivalent.
B. Cable Access: The standard UPS available shall accommodate side, top and
bottom entry cables.
C. Ventilation and Heat Rejection: The UPS shall be designed for forced aircooling. Air
inlets shall be provided from the front bottom of the UPS
enclosure. Air exhaust shall be from the top or side portions of the unit.