AUBER INSTRUMENTS
is below (H + Hy). For compressor based dehumidifier, the Hyd value should
not be set too small to prevent frequent cycling.
Note 4. HyH, Humidifier Hysteresis Band:
This is the differential band between turn on and turn off the humidifier. It is set
to the lower side of the humidifier set point (H - Hy). The humidifier will turn on
when humidity is below (H - HY – HyH), and turn off when humidity is above (H
– Hy).
For example, if Set Humidity H = 50%, Hy = 5%, Hyd = 3%, HyH = 2%, then
the humidifier will turn on when process humidity is lower than 43% (H - Hy -
HyH) and turn off when process humidity is above 45% (H - Hy). The
dehumidifier will turn on when process humidity is above 58% (H + Hy + Hyd)
and turn off when process humidity drops below 55% (H - Hy).
Note 5. OFS, Humidity Offset:
OFS (Humidity Offset:) is used to compensate the error produced by the
sensor or input signal itself. For example, if the unit displays 37% when the
actual humidity is 32%. Set parameter OFS = - 5 will make the controller
display 32%. The displayed process humidity = actual measured humidity +
OFS.
Note 6. AS, Anti-short Cycle Delay:
The Anti-short is the delay time to turn on the dehumidifier. If the dehumidifier
is compressor based, compressor should not be turned on immediately when it
is at high pressure (just after turned off). Otherwise, it may shorten the life of
compressor. The Anti-Short cycle delay function can be used to prevent the
rapid cycling of the compressor. It establishes the minimum time that the
compressor remains off (after reaching cutout) before turns on again. The
delay overrides any controller demand and does not allow the compressor to
turn on until the set time-delay value has elapsed. It gives time to release the
refrigerant pressure through evaporator. It typically set to 4- 6 (minutes). The
unit is in minutes. This setting is only valid for dehumidifying control.
Note 7. PrG, Program Mode:
When PrG is set to "ON", user can program up to 8 steps (Section 5). When
set it to "OFF", this multi-step function is disabled and controller is in single
step mode. User can only set "H-1" value (without timer t-1) when disabled.
Please be aware that if your controller is in single step mode, the green "RUN"
indicator will be off at all time. The start key, pause key and STEP key are
disabled. You can check the dehumidifier indicator (red on the left) and
humidifier indicator (green on the right) for the socket output status. When the
light is on, the corresponding socket will be activated.
Note 8. A-M, Power Outage/Startup Mode:
This parameter determines what the controller should do in an event of power
interrupt or outage. It also decides how the controller starts the program while
powered up. A-M can be set to three modes: C, S and M.
Mode C. After being powered on, the controller will continue the program from
the where it was powered off. For example, if step 3 is set for 40% and 5
hours, the power was interrupted at 2.1 hours. Then, when the controller power
up, the controller will continue to control at 40% for 2.9 hr.
Mode S. The controller will run the program from step 1 every time the
controller is powered up. This is suitable for situations where the power never
fails, or when the program mode "PrG" is set to "off".
Mode M. The program will be held at the step at which the controller was
powered off. The controller will hold the humidity at the set value. The
controller lower display will flash "hold" and process humidity alternatively. This
2018.06
mode is suitable for situations where the operator's attention is needed after
power interruption occurs.
Note 9. SFA, Sensor Failure Operation:
The SFA defines how the output would be if the sensor fails. It can be set to 0-
0, 0-1 or 1-0. Please refer to Table 3 for details. For example, in some
applications, you may want the dehumidifier to be working and the humidifier to
be off when sensor fails. Hence you need to set SFA to "1-0".
Table 3. Output of the controller when sensor fails.
SFA
Controller output when sensor fails
0-0
dehumidifier off, humidifier off
1-0
dehumidifier on, humidifier off
0-1
dehumidifier off, humidifier on
Note 10. TIM, Time unit setting:
The Time defines the timer unit setting for its timer function. It can be set to
hour (H) or minute (M). By default, Time is set to H.
Note 11. PSD, App access code (for HD220-W model only):
To prevent the operator from changing the settings by accident over the
AuberSmart App, this access code is required. The default value is 666.
6 8.9
PV
3 6.8
SV
SET
5 sec
AH
High Limit
PV
20.0
Alarm
SV
SET
AL
PV
Low Limit
20.0
Alarm
SV
SET
Humidity Control
HY
PV
Hysteresis Band
1.0
SV
SET
HYD
Dehumidifier
PV
5.0
Hysteresis Band
SV
SET
HYH
Humidifier
PV
5.0
Hysteresis Band
SV
SET
OFS
PV
Humidity Offset
0
SV
Figure 3. Flow chart of setting up parameters.
WWW.AUBERINS.COM
6 8.9
PV
End
3 6.8
SV
SET
App
PSD
PV
Access Code
666
SV
SET
TIM
PV
Time Unit
H
SV
SET
PV
SFA
Sensor Failure
SV
0-0
Operation
SET
A-M
PV
Power Outage/
S
Startup Modes
SV
SET
PV
PRG
Program Modes
ON
SV
SET
SET
AS
Anti-short
PV
Cycle Delay
M 6
SV
P3/5