AuCom CSX-007 Manual del usuario - Página 11

Navegue en línea o descargue pdf Manual del usuario para Controlador AuCom CSX-007. AuCom CSX-007 12 páginas.
También para AuCom CSX-007: Manual del usuario (13 páginas)

SCR I
Model
CSX-007
CSX-015
CSX-018
10500
CSX-022
15000
CSX-030
18000
CSX-037
51200
CSX-045
80000
CSX-055
97000
CSX-075
168000
CSX-090
245000
CSX-110
320000
7.4 General Technical Data
Mains Supply
Mains voltage (L1, L2, L3)
V4 ............................................................................................. 3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
V6 ............................................................................................. 3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
Mains frequency (at start) ................................................................................................................ 45 Hz to 66 Hz
Rated insulation voltage ................................................................................................................................... 600 VAC
Form designation ............................................................... Bypassed semiconductor motor starter form 1
Control Voltage (A1, A2, A3)
CSX-xxx-xx-C1 ................................................................................................... 110-240 VAC (+ 10% / - 15%)
...............................................................................................................................or 380-440 VAC (+ 10% / - 15%)
CSX-xxx-xx-C2 ..................................................................................................................... 24 VAC/VDC (± 20%)
Current consumption (during run) ........................................................................................................ < 100 mA
Current consumption (inrush)
CSX-xxx-xx-C1 ..................................................................................................................................................... 10 A
CSX-xxx-xx-C2 ........................................................................................................................................................ 2 A
Inputs
Start (terminal 01) .................................................................................................................................. Normally open
........................................................................................... 150 k @ 300 VAC and 5.6 k @ 24 VAC/VDC
Stop (terminal 02) ............................................................................................................................... Normally closed
........................................................................................... 150 k @ 300 VAC and 5.6 k @ 24 VAC/VDC
710-02407-00J
Ferraz/Mersen Fuse
2
t
European/IEC Style
(A
2
s)
(North American Style)
6.6URD30xxxA0063
1150
(A070URD30xxx0063)
6.6URD30xxxA0125
8000
(A070URD30xxx0125)
6.6URD30xxxA0160
(A070URD30xxx0160)
6.6URD30xxxA0160
(A070URD30xxx0160)
6.6URD30xxxA0160
(A070URD30xxx0160)
6.6URD30xxxA0250
(A070URD30xxx0250)
6.6URD30xxxA0315
(A070URD30xxx0315)
6.6URD30xxxA0315
(A070URD30xxx0315)
6.6URD31xxxA0450
(A070URD31xxx0450)
6.6URD31xxxA0450
(A070URD31xxx0450)
6.6URD31xxxA0450
(A070URD31xxx0450)
xxx = Blade Type. Contact Ferraz/Mersen for options.
CSX User Manual
SPECIFICATIONS
Bussmann Fuse
Bussmann Fuse
Square Body
(170M)
170M-1314
170M-1317
170M-1318
170M-1318
170M-1319
170M-1321
170M-1321
170M-1321
170M-1322
170M-3022
170M-3022
British Style
(BS88)
63 FE
160 FEE
160 FEE
180 FM
180 FM
250 FM
250 FM
250 FM
500 FMM
500 FMM
500 FMM
11