Abt Powerline SC12-7.5 Manual del producto - Página 3
Navegue en línea o descargue pdf Manual del producto para Accesorios para cámaras Abt Powerline SC12-7.5. Abt Powerline SC12-7.5 15 páginas. Valve-regulated sealed lead acid battery
Introduction
ABT Powerline SC is a Standard Commercial battery according to Eurobat Classification design life for
standby application with 5 years . As with all ABT batteries, all are rechargeable , highly efficient,
leakage proof and maintenance free.
Technical Features
Sealed Construction
l
The construction and sealing techniques of Powerline SC guarantee leakage proof operation in any
position with no adverse effect to capacity or service life.
Electrolyte Suspension System
l
Powerline SC utilize an electrolyte suspension system consisting of microporous glass fibre separator
material. This suspension system helps to achieve maximum service life, by fully retaining the
electrolyte and preventing its escape from the separator material.
Gas Generation
l
Powerline SC incorporates a unique design that effectively recombines over 99% of the gas generated
during floating usage.
Maintenance Free Operation
l
During the life of Powerline SC, there is no need to check the specific gravity or add water etc. In fact,
there are no provisions for such maintenance functions to be carried out.
Operation In Any Orientation
l
The combination of sealed construction and it's electrolyte suspension system permits operation of
Powerline SC in any orientation (excluding continuous inverted use) without loss of capacity, service life,
or leakage of electrolyte. The Powerline SC also conforms to IEC 60896-21/22(2004).
Low Pressure Venting System
l
Powerline SC are equipped with a safe, low pressure venting system, which is designed to release excess
gas and close automatically as the internal gas pressure rising to an unacceptable level. This low
pressure venting system, coupled with the significantly high recombination efficiency, make Powerline
SC one of the safest valve regulated lead acid batteries available.
high quality alloy
l
The positive grid alloy contained high Tin and low calcium quantity in Powerline SC should provide an
extra margin of performance and service life in floating applications.
Floating Service Life
l
The expected service life of the standard model Powerline SC when used in floating application is
typically 3- 5 years; however, experience has shown that their service life often exceeds 5 years, if the
Powerline SC are operated strictly within specification.
Self Discharge -- Shelf Life
l
At temperatures of between 20 & 25 C, the self discharge rate of Powerline SC per month is
approximately 3% of the rated capacity. This low self discharge rate permits storage for up to one year
without any appreciable deterioration of battery performance.
Operating Temperature
l
Powerline SC can be used over a wide range of ambient temperatures:
~
O
O
60 C,storage -20 60 C
, allowing considerable flexibility in system design and location.
Deep Discharge Recovery
l
Powerline SC recover their capacities even after deep discharges.
o
~
O
discharge -20 60 C,charge-10
01
~