Duco DucoBox Energy Premium Manual - Página 11

Navegue en línea o descargue pdf Manual para Ventilador Duco DucoBox Energy Premium. Duco DucoBox Energy Premium 16 páginas. Installation kit
También para Duco DucoBox Energy Premium: Manual (16 páginas), Manual de instalación (2 páginas)

Duco DucoBox Energy Premium Manual
6. Calibrating flow rates
Close all windows and doors. Ensure that all duct openings in the DucoBox Energy Premium are fully closed
and that the lid of the DucoBox Energy Premium is closed. Avoid air leaks in the ventilation ducts. Open all
interior doors between the various zones.
Activate advanced mode:
1
• Scroll down to ADVANCED and press enter.
• Enter the installer's code 9876 and press enter.
Scroll down to CALIBRATION → WIZARD and press enter. The DucoBox Energy Pre-
mium calibration mode starts up. Do not start manual calibration until you see the
2
message on the display and follow the instructions on screen. Enter the flow rates
for each zone if asked to do so.
In the 'Adjust the supply vents' step, select the duct with the highest flow rate and
resistance and, using a pressure-compensated air flow meter, measure the flow rate
at this vent. If the flow rate is too high or too low, you can adjust it using the arrow
keys on the DucoBox Energy Premium. Depending on the remote control version,
this can also be done by pressing the
remote control. Adjust the flow rate so as to obtain the desired flow rate at this vent.
3
The flow rate can be fine-adjusted at the vent.
NOTE: The system needs around ten seconds to run stably when adjusting the flow
rate using the buttons on the DucoBox Energy Premium, Remote control or making
large changes at the vent. The flow rate cannot be measured correctly until after
this time has elapsed.
(lower) and
(higher) buttons on a paired
/
/
11