[Indication Function]
Normal state: LINK ashing, ALM off, I/O ON on/OFF off
LED symbol
Indication status
On
Flashing
LINK
Off
On
ALM
Flashing
Off
Alternate ashing
LINK
LINK
ALM
ALM
On
I/O
Off
For information on narrowing down the cause of a trouble occurrence,
see the following section "Troubleshooting."
[Troubleshooting]
<LINK not ashing>
Check items
Check the connection status of the slave unit. Disconnect and reconnect the slave unit.
Check the connection status of the
master unit.
<ALM on>
Check items
Check the I/O side connection of the
slave unit.
<ALM ashing>
Check items
Check the voltage of the external
power supply (24V DC) of the master
unit.
<LINK and ALM ashing alternately>
Check items
Check the address of the slave unit.
Detailed states
Transmission error
Normal
DP/DN disconnected or no power supply
I/O voltage reduction
Slave unit voltage reduction
Normal
Master unit detecting the unit ID (address)
redundant or not set
ON
OFF
Check if the LINK LED of the master unit ashes and take the following measures.
1) If the LINK of the master unit ashes and the LINK of the slave unit is on, the master unit may be
damaged. Please contact our helpdesk.
2) If the LINK of the master unit ashes and the LINK of the slave unit is off, the master unit may not
be powered (24V DC), the transmission line (DP/DN) may be partially disconnected, or the slave
unit may be damaged. Check if the master unit is powered and, if necessary, please contact our
helpdesk.
3) If the LINK of the master unit does not ash, check if the master unit is powered. Other system
errors may also occur. Refer to the User's Manual of the master unit.
Adjust the power voltage of the externally supplied power that is connected to the I/O side of the
slave unit so that it is at the rated value (21.6V to 27.6V).
As for terminal wiring, check that there is no contact or incorrect wiring of each transmission line.
Adjust the voltage of the external power supply of the master unit to lie within the range from 21.6 to
27.6V (recommended voltage is 26.4V). Check the total line length.
Review the total line length and the size of the transmission line so as not to connect a load exceeding
a supply current limit on the transmission line and, if necessary, adjust the connected load (e.g. the
supply current on the transmission line is 2A if the size is 1.25mm
The address of the slave unit is not set (255) or address redundancy occurs. Take the following measures.
1) Change the address within the range from 0 to 254.
2) Check if there is another slave unit undergoing the same ashing and, if necessary, reset the
address so as not to be redundant.
-BL296*B16F*4A20 7/11-
LED indication unit
ALM
LINK
OUT 0
IN 0
OUT 1
IN 1
OUT 2
IN 2
OUT 3
IN 3
OUT 4
IN 4
IN 5
OUT 5
OUT 6
IN 6
OUT 7
IN 7
BL296XB-16F□-4A-20
In case of an abnormal indication status, narrow down the
cause and remove the trouble based on the on/ ashing status
and the left table.
The indication status will be restored automatically after the
trouble is removed.
Measures
Measures
Measures
and the total length is 50m or less).
2
Measures
ALM
LINK
I/O 8
I/O 0
I/O 9
I/O 1
I/O 10
I/O 2
I/O 11
I/O 3
I/O 12
I/O 4
I/O 5
I/O 13
I/O 14
I/O 6
I/O 15
I/O 7
BL296SB-16F□-4A-20
BL296PB-16F□-4A-20