Danfoss 084B8070 Manual de instrucciones - Página 7

Navegue en línea o descargue pdf Manual de instrucciones para Controlador Danfoss 084B8070. Danfoss 084B8070 14 páginas.

Danfoss 084B8070 Manual de instrucciones

Operation

Display
The values will be shown with three digits, and with a setting you
can determine whether the temperature is to be shown in °C or in
°F.
Light-emitting diodes (LED) on front panel
The LED's on the front panel will light up when the relevant relay
is activated.
= Refrigeration
= Defrost
= Fan running
The light-emitting diodes will flash when there is an alarm.
In this situation you can download the error code to the display
and cancel/sign for the alarm by giving the top button a brief
push.
The buttons
When you want to change a setting, the upper and the lower
buttons will give you a higher or lower value depending on the
button you are pushing. But before you change the value, you
must have access to the menu. You obtain this by pushing the
upper button for a couple of seconds - you will then enter the col-
umn with parameter codes. Find the parameter code you want to
change and push the middle buttons until value for the parameter
is shown. When you have changed the value, save the new value
by once more pushing the middle button.
AK-CC 550A - 084B8070
Instructions RI8PR102 © Danfoss 6/2012
Examples
Set menu
1. Push the upper button until a parameter r01 is shown
2. Push the upper or the lower button and find that parameter
you want to change
3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button againt to freeze the value.
Cutout alarm relay / receipt alarm/see alarm code
• A short press of the upper button
If there are several alarm codes they are found in a rolling
stack. Push the uppermost or lowermost button to scan the
rolling stack.
Set temperature
1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button again to conclude the setting.
Reading the temperature at defrost sensor (Or product sensor, if
selected in o92.)
• A short press of the lower button
Manuel start or stop of a defrost
• Push the lower button for four seconds.