Danfoss ADAP-KOOL AK-PC 781 Manual del usuario - Página 5

Navegue en línea o descargue pdf Manual del usuario para Controlador Danfoss ADAP-KOOL AK-PC 781. Danfoss ADAP-KOOL AK-PC 781 14 páginas. Capacity controller with heat recovery

Danfoss ADAP-KOOL AK-PC 781 Manual del usuario
S4 media temp. °C
Pctrl °C
Suction status
Actual Zone
Suction superheat K
Night Setback
Load shed 1
Load shed 2
Injection ON
MT release output
MT request input
LT request output
LT release input
No. of compressors
Comp. application
Step control mode
Settings
Main switch
Cap. control mode
Manual capacity %
Reference mode
AK-PC 781 Version 4.1x
Actual media temperature measured at S4 sensor
(Only used if S4 is selected as control sensor)
Actual regulation pressure measured with Pctrl pressure transmitter (cascade
pressure)
0: Power up Controller has been powered up (power supply re-connected)
1: Stopped
2: Manual
3: Alarm
4: Restart
5: Standby
6: State off timer
7-10: State on timer
11: Unloaded
12-14: Unload cutin
15: Full loaded All capacity cutin
16: Running Capacity control is running
Actual zone for capacity regulation:
0: P0-error
1: - - Zone
2: - Zone
3: NZ
4: + Zone
5: + + Zone
Actual superheat
Status of night setback function
ON: Night (An increase of the evaporating pressure is permitted)
OFF: Normal situation
Actual status on Load shed input 1
Actual status on Load shed input 2
Status of the "Injection ON" function (earlier mentioned "AKC ON")
0: Forced closing of all AKV valves
1: Normal operation of AKC controllers
Actual status on "Comp. release" output signal from MT controller
Actual status on "Comp. request" input signal on MT controller
Actual status on "Comp. request" output signal from LT controller
Actual status on "Comp. release" input signal on LT controller
Defined number of compressors
Select the compressor application required (see the manual for further details)
0: Single step only
1: 1xComp. w. unloaders + Single step
2: 2xComp. w. unloaders + Single step
3: Comp. w. unloaders only
4: 1xVariable speed + Single step
5: 1xVariable speed + Comp. w. unloaders
6: 2xVariable speed + Single step
Selected coupling pattern for compressors
Sequential: Compressors are cut in/out in strict accordance
with compressor number
Cyclic: Runtime equalisation between compressors
Best fit: Compressors are cut in/out in order to
make the best possible fit to actual load
0: Sequential
2: Cyclic
3: Best fit
Main switch:
0: MAN (The compressor capacity will be controlled manually)
1: OFF (The capacity control will be stopped)
2: AUTO (The capacity is controlled by the PI controller)
Manual setting of compressor capacity
The value is in % of total capacity controlled by the controller
Displacement of suction pressure as a function of external signals
0: Reference = set reference + night offset + offset from external 0-10 V signal
1: Reference = set reference + offset from P0 optimization + night offset
Menu operation RC8CE202 © Danfoss 03/2013
Capacity control has been stopped ("Main switch" = OFF or
"Control mode" = OFF)
Capacity is controlled manually ("Control mode" = MAN)
Capacity control is in alarm condition (fx. alarm on Po Min
or Pc Max)
Capacity control is waiting for elapse of "Restart time"
Capacity control is ready to start
ON:
Regulation
OFF: Controller stopped
5