Alarm priorities

Measurements
AK error
Comp. Ctrl. temp.
S4 Cold brine supply
S3 Cold brine return
P0 °C
Comp. ctrl. Ref. °C
Compressor cap. %
Request Comp. Cap %
Cond. ctrl. temp °C
S7 warm brine °C
Pc °C
Cond. ctrl. ref. °C
Cond. cap. %
Request Cond. cap %
Settings
Main switch
Standby mode
Low P0
High S4
Low S4
High Pc/Sd
Superheat min/max
Load Shedding
P0/S4 sensor error
Misc. sensor error
Cold pump alarm
Cold pump 1 & 2 alarm
Anti freeze safety
Compr VSD safety
Comp. 1 safety
Comp. 2 safety
Comp. 3 safety
Comp. 4 safety
Comp. 5 safety
Comp. 6 safety
Pc/S7 sensor error
Blocked air flow
Fan safety
Max def. time
AKM menu: "For DANFOSS only"
This menu contains data and setting values for special internal controller functions.
Do not change the stated values.
AK-CH 650 Version 2.0x
When "ON", the controller is in alarm condition.
Actual temperature for compressor control
Actual cold brine supply temperature measured with S4 temp. sensor
Actual cold brine return temperature measured with S3 temp. sensor
Suction pressure in °C. (Measured with the pressure transmitter)
Actual reference temperature for compressor control
Cut-in compressor capacity in % (of total capacity)
Reference for compressor capacity (deviations may be due to time delays)
Actual temperature for control sensor (Pc or S7)
Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Condensing pressure in °C. (measured with the pressure transmitter)
Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cut-in condenser capacity in % (of total capacity)
Reference for condenser capacity
Main switch:
The alarm priority of the following alarms can be changed:
High priority is defined with setting = 1
Medium priority is defined with setting = 2
Low priority is defined with setting = 3
Overriding the alarms is defined with setting = 0
Regulation has stopped
Minimum safety limit for suction pressure P0 has been violated
High alarm limit for S4 has been exceeded
Low alarm limit for S4 has been exceeded
Safety limit for condensing pressure Pc /discharge gas temperature is exceeded
Superheat i suction line to low / high
Load shedding has been activated
Sensor signal for P 0 / S4 is defective
Sensor signal for Ss, Sd, S3, Sc3, Saux is defective
Pump alarm. One of the pumps has fallen out. Signal from flow switch
Pump alarm. Both pumps has fallen out. Signal from flow swich
All compressors have been cut out on frost protection
Variable speed drive for compressor has been cut out on safety
Compressor has been cut out on safety
Compressor has been cut out on safety
Compressor has been cut out on safety
Compressor has been cut out on safety
Compressor has been cut out on safety
Compressor has been cut out on safety
Signal from pressure transmitter /temperature sensor is defective
The intelligent air flow monitoring of the condenser reports that a cleaning is due
Variable speed drive for condenser fans has been cut out on safety
Defrost is stopped because of too long defrost time. Check evaporator.
Service Guide RC8BV402 © Danfoss 2016-02
ON:
Regulation
OFF: Controller stopped
13