Danfoss AK-CH 650 Manual de servicio - Página 7
Navegue en línea o descargue pdf Manual de servicio para Controlador Danfoss AK-CH 650. Danfoss AK-CH 650 15 páginas. Capacity controller for water chiller
Comp 2 ... Status
VSD Speed %
Comp 1 capacity %
Comp 2 ...capacity %
Comp 1 Runtime % 24
Comp 2 ...Runtime % 24
Comp 1 Cycles / 24 h
Comp 2 ...Cycles / 24 h
Settings
Main switch
1 Min. ON-time m
2 ...Min. ON-time m
1 Min. OFF-time m
2 ...Min. OFF-time m
1 recycle time m
2 ...recycle time m
1 runtime h
2 ...runtime h
Pump control
Measurements
AK error
Comp. Ctrl. temp.
S4 Cold brine supply
S3 Cold brine return
P0 °C
Comp. ctrl. Ref. °C
Compressor cap. %
Request Comp. Cap %
Cond. ctrl. temp °C
S7 warm brine °C
Pc °C
Cond. ctrl. ref. °C
Cond. cap. %
Request Cond. cap %
Cold pump running
Flow switch status
Pump 1 safety
Pump 2 safety
Settings
Main switch
Cold Pump ctrl.
Pump cycle time
Pump switch time
Pump alarm delay
AK-CH 650 Version 2.0x
As above for compressor no. 2 to 6
The present speed of the compressor motor controlled by the frequency converter
Actual cut-in capacity on this compressor
As above for compressor no. 2 to 6
Running time for compressor 1 in percent within the past 24 hours
As above for compressor no. 2 to 6
Number of compressor starts during the past 24 hours
As above for compressor no. 2 to 6
Main switch:
Minimum duration of ON period
As above for compressor no. 2 to 6
Minimum duration of OFF period
As above for compressor no. 2 to 6
Minimum period of time between two successive starts.
As above for compressor no. 2 to 6
Compressor's total run time in hours
As above for compressor no. 2 to 6
When "ON", the controller is in alarm condition.
Actual temperature for compressor control
Actual cold brine supply temperature measured with S4 temp. sensor
Actual cold brine return temperature measured with S3 temp. sensor
Suction pressure in °C. (Measured with the pressure transmitter)
Actual reference temperature for compressor control
Cut-in compressor capacity in % (of total capacity)
Reference for compressor capacity (deviations may be due to time delays)
Actual temperature for control sensor (Pc or S7)
Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Condensing pressure in °C. (measured with the pressure transmitter)
Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cut-in condenser capacity in % (of total capacity)
Reference for condenser capacity
Reading of pump status
0: Pumps have stopped
1: Cold pump 1 is in use
2: Cold pump 2 is in use
3: Both pumps are in use
Current status for flow switch input
Actual status for input "Pump 1"
Actual status for input "Pump 2"
Main switch:
Choice of pump operation
0: Both pumps are stopped
1: Cold pump 1 is in constant use
2: Cold pump 2 is in constant use
3: Both pumps are in constant use
4: Off set of operational time between the two pumps. Start before stop
5: Off set of operational time between the two pumps. Stop before start
The operational times of the pumps before pump switch is carried out (pump's opera-
tional time before changeover to the other pump)
Overlap time during pump changeover where both pumps are in use or break time
when switching between two pumps (only relevant if "Cold Pump ctrl" is set to 4 or 5)
Delay on pump alarm before alarm is activated and automatic pump changeover car
ried out (only if "Cold Pump ctrl" is set to 4 or 5)
Service Guide RC8BV402 © Danfoss 2016-02
ON:
Regulation
OFF: Controller stopped
ON:
Regulation
OFF: Controller stopped
7