9. Flow Direction: Install so the flow direction
match es the arrow marked on the body.
10. For best performance, install in well drained
hor i zon tal pipe, properly trapped if a steam
service ap pli ca tion.
11. Valves are not to be direct buried un der ground.
12. Insulation may be applied as indicated in Figure
2. Drainage away from the packing area must
be ensured when fully installed, sealed and
lagged for outdoors installation.
13. Undue piping stress/strain or bending torques
may not be transmitted through the control
valve body. One pipe (inlet or outlet) should
be anchored rigidly for piping that is "hot" or
"cold" with respect to ambient temperature;
the re main ing pipe (inlet or outlet) should be
supported and guided to ensure uni di rec tion al
expansion/con trac tion.
C. Air Supply:
1. Use a desiccant dried, instrument quality air
supply. Such a supply is recommended for
outdoor installations, and is required in areas
of freezing weather conditions.
IV. STARTUP
A. General:
1. Ensure that the Model 987 unit has been
properly adjusted and calibrated, including
the positioner if installed.
2. Recommend startup to be in a "manual"
mode. This procedure assumes double block
(iso la tion) and bypass valves for the "control
valve station". See Figure 1.
3. Start with either of the two block valves closed,
with the other open. The bypass valve should
be closed. Pressurize system if possible/
prac ti cal.
4. Back out the airset's adjusting screw until
loose.
5. Turn on air supply pressure.
IOM-987
Limit of
Bonnet
Insulation
2. If air supply contains moisture and /or
lubricating oil, the air should be filtered with a
coalescing type of filter prior to use in stroking
the actuator.
3. Failure to remove moisture will cause corrosion
to the internals of the actuator casings.
4. Connections for the air supply are 1/4" female
NPT. Use a suitable pipe thread sealant when
installing the pipe or tube fitting. DO NOT
allow sealant to enter the tube/pipe.
SECTION IV
6. Adjust the air supply airset (filter-regulator)
to the proper level as indicated as follows:
7. Place loop controller into "manual" mode. Vary
setting from minimum – mid-range – max i mum
SIG output. Observe response of con trol
valve unit to these changes of input SIG. The
valve should fully stroke at the variation from
minimum SIG to maximum SIG; the mid-range
SIG should have the valve stem travel at/near
1/2 open.
DO NOT WALK AWAY AND LEAVE A MANUALLY
CONTROLLED CONTROL VALVE UNATTENDED!
Figure 2: Body Insulation
Bench Setting
Airset Output
psig
(Barg)
psig
5–15
(.34–1.0)
15–60
(1.0–4.1)
CAUTION
(Barg)
20
(1.4)
75
(5.2)
3