7.6
Installation scenarios 
 
 
Note: The EAN ESP filters can be fireproofed. Only the front panel access door needs to remain accessible.  
 
 
7.6.1
AOM EAN ESP filters can be installed using different configurations based on the overall total airflow and the 
requirements of the filtration efficiency.  
 
Single pass filtration 
Single pass unit installed outdoors  
with a protective weather cover 
 
7.7
 Installation  
 
 
Note: When properly maintained, the Electrostatic Precipitator will ensure high efficiency filtration of smoke and grease 
particles.  To maximise the unit's capacity, it is recommended to place the units as close as possible to the kitchen exhaust 
hoods and on the negative side of the fan, thus ensuring that grease is filtered prior. Grease build up in ducts and fans is both a 
health and safety hazard.   
 
 
 
Note: The EAN ESP unit can be set up for the airflow from right to left or left to right. When ordering the unit, specify the 
airflow direction to the AOM Representative. 
 
 
7.7.1
The EAN ESP unit is designed to be positioned within the kitchen exhaust duct run.  
7.7.2
The ideal installation position is as close as possible to the kitchen exhaust hood. This is also the best position to 
maintain and clean the unit.  
7.7.3
The EAN ESP unit should be installed in a position with easy access for cleaning purposes. See the maintenance space 
requirements on the above figures and the below requirements for access and cleaning. 
21/54 Beach Street Kogarah NSW 2217     Tel Sales 1300 903 788     Service 1300 904 088 
rev 1, 22/09/2016 
 
 
 
Stacked 
EAN stacked configurations for higher 
airflows (EAN 600T, 800, 1200) 
 
 
 
www.aomaus.com.au    email [email protected] 
 
 
 
AOM AUSTRALIA 
 
 
Double pass filtration 
High contaminant exhaust &/or sensitive 
discharge point requires very high 
filtration efficiency 
 
 