4

Settings

If a floor sensor is used, please be aware of the following:
• The floor temperature is measured where the sensor is
placed.
• The temperature of the bottom of a wooden floor can
be up to 10 degrees higher than the top.
• Floor manufactures often specify the max temperature
on the top surface of the floor (usually 27-28˚C).
• Always use a floor sensor to control floor heating.
Without a floor sensor, the temperature control may be
less accurate and you risk overheating the floor.
Thermal
Examples of
resist-
flooring
ance
[m²K/W]
0,05
8 mm HDF based
laminate
0,10
14 mm beech
parquet
0,13
22 mm solid oak
plank
< 0,17
Max. carpet
thickness suitable
for floor heating
0,18
22 mm solid fir
planks
8
DEVIreg™ 330 (+5 to +45°C)
Details
> 800 kg/m³
650 - 800 kg/m³ 31˚C
> 800 kg/m³
acc. to EN 1307 34˚C
450 - 650 kg/m³ 35°C
Approximate
setting for
25˚C floor
temperature
28˚C
32˚C
Installation Guide