Danfoss ECL Comfort 110 Manual del usuario, instalación y mantenimiento - Página 10

Navegue en línea o descargue pdf Manual del usuario, instalación y mantenimiento para Termostato Danfoss ECL Comfort 110. Danfoss ECL Comfort 110 19 páginas. Application 130
También para Danfoss ECL Comfort 110: Ficha de datos (8 páginas), Manual de instalación (8 páginas), Manual de montaje (8 páginas), Manual rápido (2 páginas), Manual rápido (2 páginas), Manual rápido (2 páginas)

Danfoss ECL Comfort 110 Manual del usuario, instalación y mantenimiento
Application
P1 exercise (pump exercise)
Setting range
ON / OFF
Exercises the pump to avoid blocking in periods without heat demand.
ON:
The pump is switched ON for 1 minute every third day around noon.

OFF:

The pump exercise is not active.
M1 exercise (valve exercise)
Setting range
ON / OFF
Exercises the valve to avoid blocking in periods without heat demand.
ON:
The valve receives a signal to open and close every third day around
noon.
OFF:
The valve exercise is not active.
P1 frost T (frost protection)
Setting range
OFF / -10 ... 20 °C
When the DHW temperature is below the set temperature in 'P1 frost T', the controller automatically
switches ON the circulation pump to protect the system.
No frost protection.
OFF:
-10 ... 20:
The circulation pump is ON when the flow temperature (S3) is below
the set value.
P1 heat T (heat demand)
Setting range
-20 ... 50 °C
When the desired flow temperature is above the set temperature in 'P1 heat T', the controller
automatically switches ON the circulation pump to meet the heat demand.
-20 ... 50:
The circulation pump is ON above the set value.
18
VI.KT.F2.02
7000
7022
Factory setting
OFF
7023
Factory setting
OFF
7077
Factory setting
10 °C
7078
Factory setting
20 °C
© Danfoss 06/2008
DH-SMT/DK
Standby T (standby temperature)
Setting range
5 ... 40 °C
Set the desired flow temperature at standby.
5 ... 40:
Desired standby flow temperature.
Ext. (external override)
Setting range
OFF / SETBACK / COMFORT
Choose mode for 'Ext.' (external override).
The override can be activated for setback or comfort mode. For override, the controller
mode must be AUTO (scheduled operation).
OFF:
The controller's schedule is not overridden.
SETBACK:
The controller is in setback mode when terminals 11 and 12 are short-
circuited.
COMFORT:
The controller is in comfort mode when terminals 11 and 12 are short-
circuited.
Min. on time (min. activation time gear motor)
Setting range
2 ... 50
The min. pulse length in milliseconds for activation of the gear motor.
Setting
2
10
50
The setting should be kept as high as acceptable to increase the lifetime of the actuator.
VI.KT.F2.02
DH-SMT/DK
7093
Factory setting
10 °C
7141
Factory setting
OFF
7189
Factory setting
Value x 20 ms
40 ms
200 ms
1000 ms
© Danfoss 06/2008
3
19