Adjustment spindles location
Note
Remove lockplate before thermostat
adjustment. Replace lockplate after
adjustment (if desired).
RANGE
See printed instruction on top of control
increase temp. (warmer): turn CW
decrease temp. (colder): turn CCW
(use adjustment knob)
Determination of differential
For KP w/ vapor charge and auto. reset (KP 61, KP 62, KP 63, KP 68, KP 69): Use graphs to determine correct differential.
Example:
HSP = 5.6 °C (45 °F) =>
LSP = 0 °C (32 °F)
© Danfoss A/S (AC-MCI / jmn), 2013-11
DIFF (from graph):
7.2 °C (13 °F) (value which has to be
set on diff. scale).
DKRCC.PI.CA0.C1.22 / 520H8304
DIFFERENTIAL
See printed instruction on top of control
(use adjustment knob or screwdriver)
For KP w/ adsorption charge (KP 71, KP 73, KP 75, KP 77, KP 79, KP 81):
The differential will be HSP less LSP
Example:
HSP – LSP = DIFF.
7 °C – 5 °C = 2 °C
(45 °F)(35 °F) (10 °F)
Note:
(Load Option A)
(Load Option B)
CUT-IN
= HSP or
CUT-IN
CUT-OUT = LSP
CUT-OUT = HSP
See "Wiring"
Increase: turn CW
decrease: turn CCW
= LSP