Danfoss vlt soft starter mcd 500 Manual de instrucciones de instalación - Página 15
Navegue en línea o descargue pdf Manual de instrucciones de instalación para Unidad de control Danfoss vlt soft starter mcd 500. Danfoss vlt soft starter mcd 500 17 páginas. Usb module
También para Danfoss vlt soft starter mcd 500: Manual de instrucciones de instalación (6 páginas), Instrucciones de instalación (5 páginas)
MCD Modbus Module Instructions
11.8.2. Programmable Parameters
The Remote Operator offers the following programmable parameters:
Parameter
Number
1
2
3
4
5
6
7
8
9
Remote Operator Reset pushbutton is always enabled.
RS485 Network reset and forced communication trip functions are always enabled.
N.B.!:
Remote Operator Par. 9
output for models MCD5-0021B ~ MCD5-0068. Use Par. 9 in conjunction with Par. 6
Motor FLC
Description
Default
Setting
RS485 network
4
baud rate
(9600 baud)
RS485 network
20
satellite address
RS485 network
0 seconds
timeout
(= off)
RS485 network
1
protocol
(AP ASCII)
Modbus protocol
0
parity
(no parity)
Motor FLC (A)
10
Analog output
100
4 mA offset (%)
Start, Stop,
0
Quick stop
function disable
Current ÷ 10
0
Current
as follows:
1.
Set Par. 6 to a value 10 times greater than the actual motor nameplate FLC
(e.g. for actual FLC = 4.6 A, set Par. 6 to 46).
2.
Set Par. 9 = 1.
MG.17.F5.02 - VLT® is a registered Danfoss trademark
Appendix A - Modbus Control via Remote Operator
Adjustable Range
2 = 2400 baud
3 = 4800 baud
4 = 9600 baud
5 = 19200 baud
6 = 38400 baud
1 to 99
0 to 100 seconds
1 = AP ASCII protocol
2 = Modbus RTU protocol
0 = no parity
1 = odd parity
2 = even parity
3 = 10-bit transmission
1 to 2868
80 to 120
0 = Remote Operator and Network start, stop, quick stop
function enabled.
1 = Remote Operator start, stop, quick stop function
enabled. Network start, stop, quick stop function disabled.
2 = Remote Operator start, stop, quick stop function
disabled. Network start, stop, quick stop function enabled.
3 = Remote Operator start, stop, quick stop function
disabled. Network start, stop, quick stop function disabled.
,
0 = off (required for models MCD5-0084B ~ MCD5-1600C)
1 = on (required for models MCD5-0021B ~ MCD5-0068B)
10
÷
normalises the displayed current and analog
15