R e l a y : C o n t i n u o u s
P o s i t i v e S a f e : O N
L a t c h i n g : O N
R e l a y : C o n t i n u o u s
P o s i t i v e S a f e : O N
L a t c h z o n e 1 : O N
L a t c h z o n e 2 : O N
The top screen shows the pre-alarm setup for a one zone
system, the bottom screen shows the two zone system.
The parameters for each option are as follows;
Relay: Continuous or Impulse
Controls how the main alarm relay operates in an
alarm condition. Continuous means the relay will
remain activated after the alarm has passed. Impulse
means the relay will activate for 20 seconds and then
revert back to its normal state.
Positive Safety: ON or OFF
ON enables Positive Safety which controls how the
main alarm relay operates. It is advisable to enable this
function as it works as a fail safe should you lose
power to the BX216. NOTE: Changing this option alters
how you wire the unit to the gas valve, refer to wiring
diagrams.
Latch Zone 1 / Latching: ON or OFF
Determines whether the main alarm LED remains lit
after the alarm has passed. If set to ON the LED will
remain lit after an alarm condition until the Reset
button is pressed. If set to OFF the LED will turn off as
soon as the alarm condition has passed.
Latch Zone 2: ON or OFF
As above.
Moving the cursor down to the
move you down to the next screen shown below.
S i r e n : A c t i v e
A d v a n c e d f e a t .
B a c k
Siren: Active or Mute
Active will enable the onboard audible siren in the
event of an alarm. Mute disables it.
You can check the status of the siren by looking at the
Siren LED on the fascia. If it is green it is enabled, if it is
red it has been disabled.
To go back to the top menu, press Enter when on
w: www.duomo.co.uk
-
and pressing Enter will

Advanced Features

P a s s w o r d c h a n g e
D a t a l o g g e r
P r i n t
T e s t p r o b e s
F a c t o r y r e s e t
B a c k
The advanced features menu has five options as detailed
in the two screens above. Scroll down to the
Enter to move down to the second screen and
back to the first screen. Select Back to go to the first menu
screen.

Password Change

Select this option to change the password that you use
to access the setup menu of the BX216.
0 1 2 3 4 5 6 7 8 9
The screen above appears. Use the left and right keys and
the Enter key to select a four character password. As each
number is selected it appears as below.
0 1 2 3 4 5 6 7 8 9
Once you have selected your four characters 'Confirmed'
will appear on the screen and the password is set.
0 1 2 3 4 5 6 7 8 9
Datalogger
The BX216 stores information on board about the
attached sensors and any detected alarms since
installation.
The complete list of events stored by the datalogger is;
pre-alarms, alarms, faults, blackouts, resets, low battery,
probes enabled / disabled, hard reset.
.
Use the up and down keys on the keypad to move
-
t: 01905 797989
-
N e w P a s s w o r d
N e w P a s s w o r d
1 2 3 4
N e w P a s s w o r d
C o n f i r m e d
1 2 3 4
f: 01905 774296
|
and press
to go
© Duomo (UK) Ltd. 2007