BX308 XP Gas Detection Controller
Advanced Functions
Advanced Functions
▼▲ - Choose menu option
ENTER - Choose advanced functions
Change password
Change password
Datalogger
Print
Test probes
Move with the ◄► buttons over the desired number
and press "ENTER", each time the number selected will
light up. Proceed with the insertion until all four numbers
are turned on.
Once entered, the word "CONFIRMED" lights up.
Memorize your password and don't forget it! If you forget
your password you can find the "PUK" number written on
the warranty sheet.
From this moment, to access the ECU programming, the
new Password must be entered. After the change the
program switches to the next function. "Data logger"
Datalogger
Move with the ▼▲ buttons using either x1 or x10 to
advance through events.
All security and general fault events are stored in the data
logger, including network blackouts, battery operation or
discharge, etc.
All data is stored with codes, each code corresponds to an
event. See table below for error code event types:
Type of Event
1 Pre-alarm
2 Alarm
3 Generic Fault Sensor
4 Black Out
5 Voltage Recovery
6 Low Battery
10 Sensor off
11 Device Reset
12 Clock Battery
t: 01905 797989
e: [email protected] | w: www.duomo.co.uk
Power
Pre Alarm
Battery
Main Alarm
OL Probes
Exit Alarm
OL Battery
Siren Status
Fault
Power
Pre Alarm
Battery
Main Alarm
OL Probes
Exit Alarm
OL Battery
Siren Status
Fault
Code
E00-S01
E01-S01
E02-S01
E03-C00
E04-C00
E05-C00
E09-S01
E10-C00
E11-C00
Test Probes (Sensors)
Process to functional control the gas detection sensors.
Conventional probes transmit the signal to the control unit in
current from 4 to 20 mA values.
4 mA - No gas
20 mA - Gas alarm level threshold.
In the start-up phase the cursor positions itself on sensor 1.
Voltage and the current detected by the sensor is displayed.
Move to desired sensor with the ◄► buttons
V=00.6V
I=04.0mA
12345678
Maintenence Program
This ensures that gas flow is not interrupted during
maintenance operations and inhibits the external siren.
The interruption period is managed directly by the technician
based on the size of the installation. Position yourself above
the word: "maintenance: 00"
Press "ENTER" button to adjust the maintenence time period
(15 - 30 - 45 - 60 minutes)
N.B. At the end of the countdown the device returns to
normal operating status. During the maintenance period "in
Maintenance" and remaining minutes are displayed.
Maintenance interruption
If the job ends before the set time, pressing the "RESET"
button exits the maintenance cycle.
Functional test
A function test should be carried out every 6 months
minimum. Using calibration gas of the target gas over the
level of the alarm threshold the sensor can be tested. This
teset the sensor is reacting and the the correct functions are
activated by the controller.
At least once a year A more accurate check must be
carried out by a specialised technician who must issue the
verification certificate with the Duomo TS1007 tester.
The decommissioning of the system must be carried out by
a specialised technician.
10
Power
Pre Alarm
Battery
Main Alarm
OL Probes
Exit Alarm
OL Battery
Siren Status
Fault