In case of alarm
Extinguish any naked flames.
Do not switch lights or electrical devices on or off.
Open all windows and door to increase ventalation.
If the ALARM LED is off the levels of gas have dropped. A responsible, qualified person is now safe to find the cause of the alarm.
If the alarm sound reamins constant and the cause is not evident or not possible to eliminate turn off the emergency isolation valaves to the area
and contact your gas provider emergency line. They will advise accordingly.

Troubleshooting

The Problem
If the device does not start up.
If the Fault LED lights up, the system reports
an error status.
If the Over Load Probe LED lights up.
If the Over Load Battery LED lights up.
If the control unit is repeatedly issuing an
alarm.
If the control unit is issuing an alarm and
does not shut off the devices connected to
it.
If a 12Vdc solenoid valve is connected to the
BX308/xp, which does not work well
Check that the power supply is correctly connected. If powered by the battery, check that the
is power is
correctly connected.
Possible cause: The input current loop is interrupted or the sensor is not powered.
Solution: Check the connections between the sensor and the control unit for interruption. Also
check presence of a voltage around 12 VDC between the "+ V" and "GND" terminals of the
reference input.
Check that the power polarity has not been inverted, that no short-circuit is present, that the
sensors were not damaged during installation, that no excessive current absorption is present.
Check that the connection cables are not short-circuited, that the polarity has not been
inverted, or that the battery is not damaged.
Check that there are no gas leaks.
If the alarm signal and the FAULT indicator light turn on together, check the sensors.
Check that the wiring is correct and that the jumper that carries power to the relay has
been set properly. All relays must be free from electrical power. Check the drawing of the
connections.
Direct connection of 12Vdc solenoid valves or sirens to the BX308xp is not permitted.
An external power unit must always be used. The BX308xp gives a max current of 200mA.
The Solution