Duomo CO100Ar Manual

Navegue en línea o descargue pdf Manual para Accesorios Duomo CO100Ar. Duomo CO100Ar 4 páginas.

Duomo CO100Ar Manual
Application
Duomo is recognised within the gas industry for
providing a comprehensive range o ow cost, high
reliability gas detection for many applications. We
have installed and commissioned natural gas and
carbon monoxide sensors in applications such as
boiler rooms, kitchens, car parks, aircraft hangers,
factories and shopping centres. The CO100Ar
constantly monitors the carbon monoxide levels in
its environment. The elec trochemical sensor
technology provides
monoxide. Rugged construction and IP55 protective
rating make this unit ideal for damp conditions such
as car parks. The CO100Ar can be used as a stand
a l o n e i n t r u m e n t o r c a n b e c o n n e c te d t o t h e
BX444M, GS300M, GS100M and BX150 controllers. A
20mA signal will be derived from the device when
alarm thresholds are reached. These are 300ppm
instantaneous alarm, 100ppm alarm in 10 minutes,
30ppm alarm in 12 hours. This device, in conjunction
with the above mentioned controllers can be used
to control gas valves, sirens or air extract systems.
i
w: www.duomo.co.uk
-
c detection of carbon
DO NOT TEST THIS SENSOR WITH ANYTHING OTHER THAN DUOMO
TEST GAS, 350ppm CARBON MONOXIDE IN AIR.
above this will damage the sensor and shorten sensor life.
12 - 24V DC supply
IP55 protective rating
IP65 sintered head
Electrochemical sensor technology
4 - 20mA linear output and TWA
CE cer
d No. 96125
BS EN50291 Compliant
3 year guarantee (from date of
manufacture)
Operation
The CO100Ar is a carbon monoxide sensor which
provides both a linear 4 - 20mA output and a time
weighted average output. The sensor automatically
calculates carbon monoxide concentration relative
to time (Time Weighted Average) and will give a
20mA output from terminal 3 should the carbon
monoxide levels remain above predetermined
levels for extended periods. This is useful when
carbon monoxide levels are likely to drop rapidly
when extract fans are boosted. Thus the TWA
threshold may not be reached but an indication of
actual carbon monoxide levels is required for BMS
and ventilation interfacing. The unit also has volt-
free relays for sensor fault, CO alarm level (at
300ppm) and a time weighted average alarm.
CAUTION! Carefully read the following instructions
prior to installation of this device. Always keep this
pamphlet for future reference. Ensure that the gas
detection system is wired correctly and is only used
for the purpose for which it is intended.
-
t: 01905 797989
-
CO100Ar Sensor
Concentrations
f: 01905 774296
|
© Duomo (UK) Ltd. 2016