OWNER'S MANUAL INSTALLATION INSTRUCTIONS
Table 6
Airflow Adjust Table
MODEL #
AUX HEAT RANGE (KW/CFM)
VIOLET
A
Wire
Selection
15kw
AHV08
--
15 thru 20kw
AHV12
--
AHV16
--
AHV20

SEQUENCE OF OPERATION

AHV air handler will supply airflow in a range which is more than twice
the range of a standard air handler. Each air handler size is designed
to provide nominal cooling capacities at 50F evaporator temperature
and the required airflow in order to match with any of four (4) different
air conditioner or heat pump outdoor unit sizes. Table 2 outline the
CFM range for the different AHV air handler.
The blower motor is a true variable speed motor designed to deliver
constant CFM. Constant CFM is valid for systems with total external
static pressure between 0.1 and 1.2 inches water column (25 and
174 Pa).
A. CONTINUOUS FAN
Thermostat closes circuit R to G.
Blower runs at continuous fan airflow.
B. COOLING MODE - SINGLE STAGE
If indoor temperature is above temperature set point and humidity
is below humidity set point, thermostat closes circuits R to G, R
to Y/Y2 and R to O.
NOTE:
For single stage systems, do not use the Y1
terminal.
Air handler delivers single stage cooling airflow.
C. COOLING MODE - TWO STAGE
First stage (low) cooling: Thermostat closes circuits to R to G, R
to O, and R to Y1.
Air handler delivers low stage cooling airflow.
Second stage (high) cooling: Thermostat closes circuits to R to
G, R to O, R to Y1 and R to Y/Y2.
Air handler delivers high stage cooling airflow.
D. ELECTRIC HEAT HEATING MODE
Thermostat closes circuit R to W/W1, or W2.
Air handler delivers the selected electric heat airflow.
E. HEAT PUMP HEATING MODE - SINGLE STAGE
Thermostat closes circuits R to G and R to Y/Y2.
NOTE:
For single stage systems, do not use the Y1
terminal.
Air handler delivers single stage heat pump heating airflow.
F. HEAT PUMP HEATING MODE - TWO STAGES
First stage (low) heating: Thermostat closes circuits R to G and
R to Y1.
Air handler delivers low stage heating airflow.
Second stage (high) heating: Thermostat closes R to G, R to Y1
and R to Y/Y2.
Air handler delivers high stage heating airflow.
B
C
D
--
10kw
5kw
10kw
5kw
25kw
--
5 thru 20kw
--
25kw
5 thru 20kw
Table 7
MODEL #
BLUE Wire
A
Selection
AHV08
036
AHV12
048
AHV16
060
AHV20
060
G. HEAT PUMP HEATING WITH AUXILIARY ELECTRIC
HEAT
Thermostat closes circuits R to G, R to Y/Y2 and/or R to Y1 with
R to W/W1 or W2 (and R to O in the case of defrost).
If the thermostat calls for electric heat when the heat pump is
operating in heating or defrost, the motor will modify the airflow if
necessary. The motor will provide an airflow which is safe for the
operation of the electric heat. That airflow is the greater of the heat
pump heating airflow and the electric heat only airflow.
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property
damage.
A field fabricated auxiliary drain pan, with a separate drain
is REQUIRED for all installations over a finished living
space or in any area that may be damaged by overflow
from a restricted main drain pan. In some localities, local
codes require an auxiliary drain pan for ANY horizontal
installation.
CARE AND MAINTENANCE
The system should be regularly inspected by a qualified service
technician. Consult the servicing dealer for recommended frequency.
Between visits, the only consumer service recommended or required
is air filter maintenance and condensate drain operation.
AIR FILTER
Inspect air filters at least monthly and replace or clean as required.
Disposable type filters should be replaced. Reusable type filters may
be cleaned by soaking in mild detergent and rinsing with cold water.
The frequency of cleaning depends upon the hours of operation and
the local atmospheric conditions. Install filters with the arrows on the
side pointing in the direction of air flow. Clean filters keep unit
efficiency high.
LUBRICATION
The bearings of the blower motor are permanently lubricated.
CONDENSATE DRAINS
During the cooling season check the condensate drain lines to be
sure that condensate is flowing from the primary drain but not from
the secondary drain. If condensate ever flows from the secondary
drain, the unit should be promptly shut off and the condensate pan
and drains cleaned to insure a free flowing primary drain.
12
DUOTEC AIR HANDLER: AHV
Outdoor Unit Size
OUTDOOR UNIT SIZE (BTU)
B
C
030
024
036
030
048
042
048
042
D
018
024
036
036