8.

Reset

Should your aquarium computer not be working correctly, please carry out a reset as follows:
1. Switch off power to MultiControl.
2. a) General reset: pull the power plug. Press and hold down the "Menu" key and reconnect power plug.
Release the key. All programmed settings are deleted.
b) Reset the time-controlled slots: pull the power plug. Press and hold down the ▲ key and reconnect
power plug. Release the key. Only programmed settings for the time-controlled slots are deleted,
all other settings are maintained.
3. Release "Menu" key.
Caution: Activating the reset function will result in a loss of all programmed settings.
9.

Source of Fault

In the case of a problem, fi rst reset to the factory settings. If this does not solve the problem, please search for
the fault in the following table:
Fault
Temperature control is not
working
Display E01
Display E02
Alarm cannot be
deactivated
External devices are not
operated at the preset time
Fluctuating temperature
display
pH value is not displayed
pH value is not controlled
Fluctuating pH value
If repair is required, please return to where purchased.
14
Possible cause
Immersion heater thermostat
overriding MultiControl
Temperature sensor cable break /
Temperature sensor not connected
Temperature sensor hot-wired
Temperature sensor defect
Time setting inactive
Temperature sensor cable too close
to a power cable
Display was switched off
pH control is not activated
pH electrode cable too close to a
mains cable or a CO
reactor / the
2
values displayed during calibration
did not steady suffi ciently
Solution
Set heater thermostat 3-4° C higher
than the MultiControl
Replace or connect temperature
sensor
Replace temperature sensor
Replace temperature sensor
Check time setting and selection of
week-day
Re-locate temperature sensor
differently
Switch display on
Activate pH control
Re-locate pH electrode cable / re-
calibrate pH electrode - if necessary,
2-3 times