DANLERS COPD17M Notas de instalación
Navegue en línea o descargue pdf Notas de instalación para Sensores de seguridad DANLERS COPD17M. DANLERS COPD17M 2 páginas. Compact person detector, pir switch
Trouble shooting
Note: The COPD17M cannot be made to switch on / off according to
variance in ambient light levels.
The PIR does not detect
• Person is too far from the COPD17M switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
The PIR stops working
• Ensure the unit is mounted correctly so that no water can enter.
The PIR False triggers
• Detector is exposed to air movement on breezy days.
Precautions and Warranty
This product conforms to BS EN 60669-2-1 and BS EN 55015.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. a 10 amp circuit breaker and voltage surge protection.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected]
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
08/05/19
DANLERS Compact Person Detector can be mounted onto the end
of lighting battens via the 20mm knock out. The switch includes the
connection 20mm thread and can also be surface mounted onto an
external wall. It incorporates a passive infra-red quad sensor to detect
movement of a warm body within the detection zone (diagrams A & B).
The maximum detection range is up to 24m when mounted at the
maximum mounting height of 17 metres over 120 degrees.
If no more movement is detected within a pre-selected time, then
the PIR switch will turn the load off. This time lag can be set via the
TIME adjuster to 10 seconds, 20 seconds, 40 seconds, 80 seconds,
2 minutes 30 seconds, 5 minutes,10 minutes, 20 minutes or 40
minutes (diagram C).
The switch should only be connected to a 230V 50Hz AC supply.
These PIR switches can switch up to:
10 amps (2300W) of:
• Fluorescent lamps, either high frequency of switch start
• Incandescent or mains halogen lamps (recommended with
integral safety fuse)
They can also switch up to:
• 6 amps (1500W) of electronic or wire wound transformers.
• 6 amps (1500W) of compact fluorescent or LED lamps and drivers
(PF ≥ 0.95).
• 1 amp (250W) of Fans.
Larger loads can be switched via a contactor.