Dantherm CC 3000 Manual - Página 16

Navegue en línea o descargue pdf Manual para Controlador Dantherm CC 3000. Dantherm CC 3000 20 páginas.

Dantherm CC 3000 Manual
Air Conditioner Mode
16
Default Cooling strategies,
Description
Set Point
External Air Con unit 1 start if connected
A/C 1 off
External Air Con unit 1 stops if connected
A/C 2 on
External Air Con unit 2 start if connected
A/C 2 off
External Air Con unit 2 stops if connected
Emergency on
Fan run 100% and both A/C 1 and A/C 2 starts
Emergency off
Fan stops both A/C 1 and A/C 2 continue to run
The free cooling unit is not active, only the connected Air conditioners
A/C Status
continued
Value
27
25
29
27
38
36