UK24BAC
PICS
Service processing

BACnet object description

Object Name
Object Type / Instance
Device_Name
Device
OFFSET_DEV_ID
Analog Value
COV_MODE
Multi-state Value [1]
NODE_TYPE_[n]
Multi-state Value [n*100+0]
REL_STPT_[n]
Analog Output
OVERRIDE_[n]
Multi-state Value [n*100+1]
www.belimo.com
Belimo Gateway MP to BACnet MS/TP
(continued)
 The device supports DeviceCommunicationControl service. The execution of the service is
password protected (Password: BELIMO).
Description
[x]
[1]
This value plus the parameterized MAC
address (0...127) define the Device-ID.
Setting of the COV mode
If COV is enable, changed values will be
transmitted as broadcast (local or global).
The property COV_Increment must be
adjusted accordingly for Analog Input
objects.
Actuator type; the allocation may deviate
from the basic category with some actuators.
Note: In the event of a communications
interruption, the Gateway will discard the
affected actuator after 10 seconds and reset
the actuator type to 0. Monitoring of the
actuator is thus accomplished preferably
with this object.
Each MP node has an unambiguous series
number (e.g. 00839-31324-064-008). This
number is show in the property Description.
[n*100+0]
Setpoint for actuator setting in %
The default value can be parameterized with
property Relinquish_Default.
In the case of actuators for fire dampers, the
control must be accomplished through
override control (see OVERRIDE).
Overriding the setpoint with defined values
The default value can be parameterized with
property Relinquish_Default.
For fire dampers:
Due to safety considerations, the only
override values permitted in the case of
actuators for fire dampers are OPEN and
CLOSE.
The operating position (OPEN) must also be
repeated within 120 seconds. If the override
command is not renewed, then the Gateway
will move the actuator into safety position
(Relinquish_Default is not writable).
T9-UK24BAC • en • v1.9 • 06.2018 • Subject to changes
Values
Default
-
-
0...4'194'056
1000
22
(2
-247)
OFF
OFF
LOCAL
GLOBAL
NONE
NONE
AIR/WATER
GLOBE VALVE
FIRE
VAV/EPIV
MPL
0...100
0
NONE
NONE
OPEN
CLOSE
MIN/VMIN
MID/VMID
MAX/VMAX
13 / 20